Assessment Year | 2024 |
---|---|
Principal Product | Instrument panels, doors, consoles |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 499 |
Plant Area |
219,644
ft2
|
Annual Production | 403,000
units
|
Production Hrs. Annual | 5,680
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $438,152 | 7,730,128 |
kWh
|
$0.057 | |
Electricity Demand | $266,479 | 15,589 |
kW-mo/yr
|
$17.09 | |
Electricity Fees | $114,729 | - |
|
- | |
Natural Gas | $147,090 | 14,893 |
MMBtu
|
$9.88 | |
Waste Disposal Costs | |||||
Water Usage | $19,330 | 2,713 |
Tgal
|
$7.12 | |
TOTAL YEARLY COSTS | $985,780 | ||||
RECOMMENDED SAVINGS* | $79,147 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $1,500 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,500 | $340 |
$1,078
18,006
kWh
|
$422
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $11,930 | $4,000 |
$5,655
94,248
kWh
|
$6,275
-
kW-mo/yr
|
- | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $574 | - |
$359
5,987
kWh
|
$215
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $272 | $69 |
$169
2,824
kWh
|
$103
-
kW-mo/yr
|
- | |
05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $31,317 | $16,978 |
$(-9,630.7)
(-160,512)
kWh
|
- |
$40,947
-
MMBtu
|
|
06 | 2.7492: Use proper thickness of insulation on building envelope | $31,190 | $89,468 | - | - |
$31,190
-
MMBtu
|
|
07 | 2.4322: Use or replace with energy efficient substitutes | $2,365 | $25,500 |
$2,365
36,000
kWh
|
- | - | |
TOTAL RECOMMENDED | $79,147 | $136,355 |
$(-4.7)
(-3,447)
kWh
|
$7,015
-
kW-mo/yr
|
$72,137
-
MMBtu
|
||
TOTAL IMPLEMENTED | $1,500 | $340 |
$1,078
18,006
kWh
|
$422
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs