Assessment Year | 2023 |
---|---|
Principal Product | Coating Pieces |
NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
SIC | 3399: Primary Metal Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 49 |
Plant Area |
23,000
ft2
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $241,378 | 3,525,312 |
kWh
|
$0.068 |
Electricity Demand | $52,940 | 8,134 |
kW-mo/yr
|
$6.51 |
Electricity Fees | $44,803 | - |
|
- |
Natural Gas | $11,727 | 1,082 |
MMBtu
|
$10.84 |
TOTAL YEARLY COSTS | $350,848 | |||
RECOMMENDED SAVINGS* | $29,581 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,304 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $14,863 | $294,000 |
$14,112
176,400
kWh
|
$657
-
kW-mo/yr
|
$94
-
MMBtu
|
|
02 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $11,030 | $122,000 |
$10,928
136,597
kWh
|
$102
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,238 | $4,250 |
$2,913
36,418
kWh
|
$325
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $247 | $260 |
$247
3,088
kWh
|
- | - | |
05 | 2.7444: Close holes and openings in building such as broken windows | $203 | $76 |
$129
1,615
kWh
|
- |
$74
-
MMBtu
|
|
TOTAL RECOMMENDED | $29,581 | $420,586 |
$28,330
354,118
kWh
|
$1,084
-
kW-mo/yr
|
$168
-
MMBtu
|
||
TOTAL IMPLEMENTED | $18,304 | $298,326 |
$17,155
214,433
kWh
|
$982
-
kW-mo/yr
|
$168
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs