| Assessment Year | 2022 |
|---|---|
| Principal Product | Bare Printed Circuit Boards |
| NAICS | 334412: Bare Printed Circuit Board Manufacturing |
| SIC | 3672: Printed Circuit Boards |
| Sales Range | $10 M to 50M |
| # of Employees | 350 |
| Plant Area |
150,000
ft2
|
| Annual Production | 2,777,230
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $468,285 | 11,233,744 |
kWh
|
$0.042 |
| Electricity Demand | $340,917 | 42,851 |
kW-mo/yr
|
$7.96 |
| Electricity Fees | $42,670 | - |
|
- |
| Natural Gas | $149,019 | 20,790 |
MMBtu
|
$7.17 |
| TOTAL YEARLY COSTS | $1,000,891 | |||
| RECOMMENDED SAVINGS* | $9,072 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,459 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,260 | $4,730 |
$4,965
99,302
kWh
|
$2,295
-
kW-mo/yr
|
- | |
| 02 | 2.7444: Close holes and openings in building such as broken windows | $964 | $45 |
$791
15,826
kWh
|
$173
-
kW-mo/yr
|
- | |
| 03 | 2.6211: Conserve energy by efficient use of vending machines | $483 | $730 |
$396
7,978
kWh
|
$87
-
kW-mo/yr
|
- | |
| 04 | 2.7135: Install occupancy sensors | $235 | $182 |
$193
3,856
kWh
|
$42
-
kW-mo/yr
|
- | |
| 05 | 2.7291: Reschedule and rearrange multiple-source heating systems | $77 | - | - | - |
$77
-
MMBtu
|
|
| 06 | 2.7111: Reduce illumination to minimum necessary levels | $54 | $40 |
$44
874
kWh
|
$10
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $9,072 | $5,727 |
$6,389
127,835
kWh
|
$2,606
-
kW-mo/yr
|
$77
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $8,459 | $4,957 |
$5,949
118,984
kWh
|
$2,510
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs