| Assessment Year | 2026 |
|---|---|
| Principal Product | Custom Tools |
| NAICS | 333514: Special Die and Tool, Die Set, Jig, and Fixture Manufacturing |
| SIC | 3544: Special Dies and Tools, Die Sets, Jigs and Fixtures, and Industrial Molds |
| Sales Range | $5 M to 10M |
| # of Employees | 50 |
| Plant Area |
40,000
ft2
|
| Annual Production | 10,000
units
|
| Production Hrs. Annual | 2,184
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $85,392 | 972,200 |
kWh
|
$0.088 | |
| Electricity Demand | $45,131 | 3,579 |
kW-mo/yr
|
$12.61 | |
| Natural Gas | $3,762 | 388 |
MMBtu
|
$9.70 | |
| LPG | $5,797 | 179 |
MMBtu
|
$32.46 | |
| Waste Disposal Costs | |||||
| Water Usage | $4,698 | 1,566 |
Tgal
|
$3.00 | |
| Water Disposal | $3,638 | 1,566 |
Tgal
|
$2.32 | |
| TOTAL YEARLY COSTS | $148,418 | ||||
| RECOMMENDED SAVINGS* | $99,817 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 4.513: Re-arrange equipment layout to reduce labor costs | $4,800 | $2,500 | - | - | - | - | $4,800 | |
| 02 | 2.7135: Install occupancy sensors | $184 | $2,514 |
$184
2,091
kWh
|
- | - | - | - | |
| 03 | 4.311: Schedule deliveries according to demand | $50,000 | $318,000 | - | - | - | - | $50,000 | |
| 04 | 2.1321: Replace fossil fuel equipment with electrical equipment | $4,769 | $50,000 |
$(-1,028.0)
(-11,712)
kWh
|
- |
$5,797
-
MMBtu
|
- | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,305 | - |
$1,305
14,859
kWh
|
- | - | - | - | |
| 06 | 2.7221: Lower temperature during the winter season and vice-versa | $3,769 | - |
$3,769
42,930
kWh
|
- | - | - | - | |
| 07 | 2.6218: Turn off equipment when not in use | $5,284 | - |
$5,284
61,150
kWh
|
- | - | - | - | |
| 08 | 2.7261: Install timers and/or thermostats | $15,624 | $1,339 |
$15,624
177,954
kWh
|
- | - | - | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,862 | $20,295 |
$2,744
31,247
kWh
|
$2,118
-
kW-mo/yr
|
- | - | - | |
| 10 | 2.8121: Apply for tax-free status for energy purchases | $9,220 | - | - | - | - | $9,220 | - | |
| TOTAL RECOMMENDED | $99,817 | $394,648 |
$27,882
318,520
kWh
|
$2,118
-
kW-mo/yr
|
$5,797
-
MMBtu
|
$9,220 | $54,800 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs