Assessment Year 2011
Principal Product Heat Exchanger Units
NAICS 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen
SIC 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment
Sales Range $100
M
to 500
M
# of Employees 800
Plant Area 1,000,000
ft2
Annual Production 90,000
pieces
Production Hrs. Annual 7,200
hrs
Location (State) Mississippi

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $718,297 17,291,736
kWh
Electricity Demand $126,194 34,167
kW-mo/yr
Electricity Fees $290,222 -
Natural Gas $320,321 60,766
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $117,843 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $37,919

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $76,988 $223,560 $52,910
1,273,709
kWh
$7,431
-
kW-mo/yr
$16,647
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $15,473 $142 $12,119
291,749
kWh
- $3,354
03 2.7124: Make a practice of turning off lights when not needed $14,805 - $7,331
176,472
kWh
$4,116
-
kW-mo/yr
$3,358
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,932 $480 $4,635
111,587
kWh
- $1,297
05 2.4221: Install compressor air intakes in coolest locations $2,936 $1,056 $1,552
37,355
kWh
$718
-
kW-mo/yr
$666
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,709 $17,527 $1,037
24,956
kWh
$284
-
kW-mo/yr
$388
TOTAL RECOMMENDED $117,843 $242,765 $79,584
1,915,828
kWh
$12,549
-
kW-mo/yr
$25,710
TOTAL IMPLEMENTED $37,919 $18,149 $25,122
604,764
kWh
$4,400
-
kW-mo/yr
$8,397
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs