| Assessment Year | 2009 |
|---|---|
| Principal Product | AIR FILTRATION SYSTEMS |
| NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
190,000
ft2
|
| Annual Production | 40,000
pieces
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $177,159 | 2,942,400 |
kWh
|
$0.060 |
| Electricity Demand | $107,878 | 9,144 |
kW-mo/yr
|
$11.80 |
| Electricity Fees | $4,891 | - |
|
- |
| Natural Gas | $88,074 | 7,403 |
MMBtu
|
$11.90 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $51,799 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $51,197 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $35,269 | $61,142 |
$15,400
225,820
kWh
|
$19,348
-
kW-mo/yr
|
$521 | - | |
| 02 | 2.3132: Recharge batteries on during off-peak demand periods | $8,753 | - | - |
$8,624
-
kW-mo/yr
|
$129 | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,780 | $462 |
$3,724
54,591
kWh
|
- | $56 | - | |
| 04 | 2.7124: Make a practice of turning off lights when not needed | $3,113 | - |
$3,067
50,950
kWh
|
- | $46 | - | |
| 05 | 2.7135: Install occupancy sensors | $602 | $1,212 |
$593
9,848
kWh
|
- | $9 | - | |
| 06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $282 | - | - | - | - |
$282
-
MMBtu
|
|
| TOTAL RECOMMENDED | $51,799 | $62,816 |
$22,784
341,209
kWh
|
$27,972
-
kW-mo/yr
|
$761 |
$282
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $51,197 | $61,604 |
$22,191
331,361
kWh
|
$27,972
-
kW-mo/yr
|
$752 |
$282
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs