Assessment Year | 2008 |
---|---|
Principal Product | Bread |
NAICS | 311812: Commercial Bakeries |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 175 |
Plant Area |
75,000
ft2
|
Annual Production | 540,000,000
pieces
|
Production Hrs. Annual | 8,112
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $476,774 | 8,885,400 |
kWh
|
$0.054 |
Electricity Demand | $54,730 | 13,898 |
kW-mo/yr
|
$3.94 |
Electricity Fees | $62,306 | - |
|
- |
Natural Gas | $478,247 | 54,946 |
MMBtu
|
$8.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $62,910 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $58,226 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $21,490 | $1,800 | - | - | - |
$21,490
-
MMBtu
|
|
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $15,879 | $1,000 | - | - | - |
$15,879
-
MMBtu
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,253 | $401 |
$10,706
321,129
kWh
|
- | $1,547 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,975 | $17,657 |
$5,356
160,719
kWh
|
$833
-
kW-mo/yr
|
$786 | - | |
05 | 2.2135: Repair and eliminate steam leaks | $2,517 | $94 | - | - | - |
$2,517
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,629 | $8,225 |
$1,206
36,189
kWh
|
$245
-
kW-mo/yr
|
$178 | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $1,094 | $1,050 |
$778
23,365
kWh
|
$200
-
kW-mo/yr
|
$116 | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $631 | $4,158 |
$629
16,550
kWh
|
- | $2 | - | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $442 | $2,040 |
$163
4,885
kWh
|
$252
-
kW-mo/yr
|
$27 | - | |
TOTAL RECOMMENDED | $62,910 | $36,425 |
$18,838
562,837
kWh
|
$1,530
-
kW-mo/yr
|
$2,656 |
$39,886
-
MMBtu
|
||
TOTAL IMPLEMENTED | $58,226 | $29,083 |
$17,268
518,037
kWh
|
$1,078
-
kW-mo/yr
|
$2,511 |
$37,369
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs