Assessment Year | 2007 |
---|---|
Principal Product | Fuel Tanks |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
105,000
ft2
|
Annual Production | 20,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $211,333 | 3,099,520 |
kWh
|
$0.068 |
Electricity Demand | $9,927 | 7,560 |
kW-mo/yr
|
$1.31 |
Electricity Fees | $95,974 | - |
|
- |
LPG | $58,571 | 2,824 |
MMBtu
|
$20.74 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $43,240 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,061 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,634 | $27,365 |
$14,523
334,473
kWh
|
$1,865
-
kW-mo/yr
|
$246 | - | |
02 | 2.8112: Combine utility meters | $15,244 | - | - | - | - | $15,244 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,294 | $247 |
$8,633
210,866
kWh
|
- | $661 | - | |
04 | 4.231: Purchase equipment instead of leasing | $1,523 | $1,575 | - | - | - | $1,523 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $545 | $5,264 |
$403
9,833
kWh
|
$110
-
kW-mo/yr
|
$32 | - | |
TOTAL RECOMMENDED | $43,240 | $34,451 |
$23,559
555,172
kWh
|
$1,975
-
kW-mo/yr
|
$939 | $16,767 | ||
TOTAL IMPLEMENTED | $26,061 | $1,822 |
$8,633
210,866
kWh
|
- | $661 | $16,767 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs