| Assessment Year | 2004 |
|---|---|
| Principal Product | Recliner Mechanisms |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | less than $500 k |
| # of Employees | 350 |
| Plant Area |
195,000
ft2
|
| Annual Production | 1,500,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $173,578 | 4,737,893 |
kWh
|
$0.037 |
| Electricity Demand | $95,587 | 10,855 |
kW-mo/yr
|
$8.81 |
| Electricity Fees | $9,159 | - |
|
- |
| Natural Gas | $443,114 | 66,692 |
MMBtu
|
$6.64 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,193 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,208 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,471 | $84,783 |
$11,300
314,872
kWh
|
$5,912
-
kW-mo/yr
|
$259 | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,737 | $318 |
$5,653
159,283
kWh
|
- | $84 | - | |
| 03 | 2.7229: Air condition only space necessary | $2,457 | $480 |
$462
13,029
kWh
|
$1,958
-
kW-mo/yr
|
$37 | - | |
| 04 | 2.2437: Recover waste heat from equipment | $1,356 | $1,624 | - | - | - |
$1,356
-
MMBtu
|
|
| 05 | 2.7261: Install timers and/or thermostats | $989 | $944 |
$974
27,452
kWh
|
- | $15 | - | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $183 | $249 |
$117
3,293
kWh
|
$63
-
kW-mo/yr
|
$3 | - | |
| TOTAL RECOMMENDED | $28,193 | $88,398 |
$18,506
517,929
kWh
|
$7,933
-
kW-mo/yr
|
$398 |
$1,356
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $23,208 | $85,101 |
$16,953
474,155
kWh
|
$5,912
-
kW-mo/yr
|
$343 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs