Assessment Year | 2004 |
---|---|
Principal Product | Catfish |
NAICS | 311710: Seafood Product Preparation and Packaging |
SIC | 2092: Prepared Fresh or Frozen Fish and Seafoods |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
136,700
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $943,422 | 22,653,000 |
kWh
|
$0.042 |
Electricity Demand | $171,667 | 47,161 |
kW-mo/yr
|
$3.64 |
Electricity Fees | $324,153 | - |
|
- |
Natural Gas | $48,984 | 5,809 |
MMBtu
|
$8.43 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $215,475 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,417 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2692: Use outside cold water source as a supply of cooling water | $111,932 | - |
$62,688
1,880,954
kWh
|
- | $49,244 | - | - | |
02 | 2.1392: Replace purchased steam with other energy source | $48,984 | - | - | - | - |
$48,984
-
MMBtu
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,687 | $150 |
$7,669
230,109
kWh
|
$1,635
-
kW-mo/yr
|
$6,383 | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $12,622 | - |
$6,103
183,119
kWh
|
$1,414
-
kW-mo/yr
|
$5,105 | - | - | |
05 | 2.3111: Heat water during off-peak periods and store for later use | $6,267 | $18,138 | - |
$5,138
-
kW-mo/yr
|
$1,129 | - | - | |
06 | 2.2447: Heat water with exhaust heat | $5,972 | - | - | - | - |
$5,972
-
MMBtu
|
- | |
07 | 3.4116: Meter recycled water (to reduce sewer charges) | $5,481 | $245,000 | - | - | - | - | $5,481 | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,277 | - |
$2,395
71,859
kWh
|
- | $1,882 | - | - | |
09 | 2.7261: Install timers and/or thermostats | $2,598 | - |
$1,455
43,659
kWh
|
- | $1,143 | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,655 | - |
$824
24,732
kWh
|
$151
-
kW-mo/yr
|
$680 | - | - | |
TOTAL RECOMMENDED | $215,475 | $263,288 |
$81,134
2,434,432
kWh
|
$8,338
-
kW-mo/yr
|
$65,566 |
$54,956
-
MMBtu
|
$5,481 | ||
TOTAL IMPLEMENTED | $31,417 | $245,150 |
$10,064
301,968
kWh
|
$1,635
-
kW-mo/yr
|
$8,265 |
$5,972
-
MMBtu
|
$5,481 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs