Assessment Year | 2002 |
---|---|
Principal Product | Pet Food Bags |
NAICS |
n/a
|
SIC | 2679: Converted Paper and Paperboard Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 260 |
Plant Area |
244,000
ft2
|
Annual Production | 150,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $318,404 | 9,264,000 |
kWh
|
$0.034 |
Electricity Demand | $177,396 | 16,703 |
kW-mo/yr
|
$10.62 |
Electricity Fees | $7,006 | - |
|
- |
Natural Gas | $195,411 | 44,744 |
MMBtu
|
$4.37 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $152,660 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $118,492 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $118,492 | $100 |
$80,086
2,330,123
kWh
|
$36,729
-
kW-mo/yr
|
$1,677 | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $12,922 | $2,070 |
$8,789
255,724
kWh
|
$3,952
-
kW-mo/yr
|
$181 | - | |
03 | 2.7231: Use radiant heater for spot heating | $2,495 | $600 |
$515
14,976
kWh
|
$1,946
-
kW-mo/yr
|
$34 | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,427 | $501 |
$3,380
98,340
kWh
|
- | $47 | - | |
05 | 2.7122: Disconnect ballasts | $1,708 | $1,602 |
$1,126
32,761
kWh
|
$558
-
kW-mo/yr
|
$24 | - | |
06 | 2.7135: Install occupancy sensors | $1,395 | $1,350 |
$1,375
40,014
kWh
|
- | $20 | - | |
07 | 2.7261: Install timers and/or thermostats | $462 | $708 |
$455
13,253
kWh
|
- | $7 | - | |
08 | 3.7198: Reduce / eliminate use of disposable product | $11,759 | $3,266 | - | - | - |
$11,759
-
lb
|
|
TOTAL RECOMMENDED | $152,660 | $10,197 |
$95,726
2,785,191
kWh
|
$43,185
-
kW-mo/yr
|
$1,990 |
$11,759
-
lb
|
||
TOTAL IMPLEMENTED | $118,492 | $100 |
$80,086
2,330,123
kWh
|
$36,729
-
kW-mo/yr
|
$1,677 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs