Assessment Year | 1997 |
---|---|
Principal Product | hydraulic cylinders |
NAICS |
n/a
|
SIC | 3593: Fluid Power Cylinders and Actuators |
Sales Range | $5 M to 10M |
# of Employees | 103 |
Plant Area |
85,000
ft2
|
Annual Production | 40,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $125,706 | 1,997,655 |
kWh
|
$0.063 |
Electricity Demand | $32,590 | 5,376 |
kW-mo/yr
|
$6.06 |
Electricity Fees | $8,212 | - |
|
- |
Natural Gas | $11,569 | 1,740 |
MMBtu
|
$6.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $116,297 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,085 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2424: Use heat in flue gases to preheat products or materials | $2,069 | $470 | - | - |
$2,069
-
MMBtu
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,291 | $3,272 |
$841
19,930
kWh
|
$450
-
kW-mo/yr
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $3,744 | $3,000 | - |
$3,744
-
kW-mo/yr
|
- | - | - | |
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,932 | $6,905 |
$6,262
147,421
kWh
|
$3,600
-
kW-mo/yr
|
$(-3,930.0)
-
MMBtu
|
- | - | |
05 | 2.6218: Turn off equipment when not in use | $2,225 | $200 |
$2,225
52,462
kWh
|
- | - | - | - | |
06 | 3.6124: Burn waste oil for heat | $790 | $1,995 | - | - |
$790
-
MMBtu
|
- | - | |
07 | 3.5248: Separate and recycle scrap metal to foundry or for sale | $81,746 | $22,500 | - | - | - | - | $81,746 | |
08 | 4.446: Automate finishing process | $18,500 | $20,000 | - | - | - | $18,500 | - | |
TOTAL RECOMMENDED | $116,297 | $58,342 |
$9,328
219,813
kWh
|
$7,794
-
kW-mo/yr
|
$(-1,071.0)
-
MMBtu
|
$18,500 | $81,746 | ||
TOTAL IMPLEMENTED | $24,085 | $23,942 |
$3,066
72,392
kWh
|
$450
-
kW-mo/yr
|
$2,069
-
MMBtu
|
$18,500 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs