| Assessment Year | 1995 |
|---|---|
| Principal Product | Furniture |
| NAICS |
n/a
|
| SIC | 2521: Wood Office Furniture |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
260,000
ft2
|
| Annual Production | 212,500
pieces
|
| Production Hrs. Annual | 2,000
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $149,005 | 2,452,521 |
kWh
|
$0.061 |
| Natural Gas | $34,237 | 5,219 |
MMBtu
|
$6.56 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $41,760 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,981 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7111: Reduce illumination to minimum necessary levels | $817 | $50 |
$817
23,740
kWh
|
- | |
| 02 | 2.3212: Optimize plant power factor | $5,164 | $2,130 |
$5,164
-
kWh
|
- | |
| 03 | 2.2428: Use flue gases in radiant heater for space heating, ovens, etc | $11,921 | $12,146 | - |
$11,921
-
MMBtu
|
|
| 04 | 2.6214: Shut off pilots in standby equipment | $678 | $20 | - |
$678
-
MMBtu
|
|
| 05 | 2.7261: Install timers and/or thermostats | $2,158 | $5,000 |
$2,158
70,926
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,824 | $4,949 |
$2,824
41,618
kWh
|
- | |
| 07 | 2.2437: Recover waste heat from equipment | $18,198 | $32,850 | - |
$18,198
-
MMBtu
|
|
| TOTAL RECOMMENDED | $41,760 | $57,145 |
$10,963
136,284
kWh
|
$30,797
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,981 | $2,180 |
$5,981
23,740
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs