Assessment Year | 1994 |
---|---|
Principal Product | Extruded Plastic Products |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
150,000
ft2
|
Annual Production | 20,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $476,313 | 9,644,197 |
kWh
|
$0.049 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,094 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $7,089 | $9,000 |
$7,089
-
kWh
|
|
02 | 2.4221: Install compressor air intakes in coolest locations | $1,830 | $1,000 |
$1,830
37,515
kWh
|
|
03 | 2.4133: Use most efficient type of electric motors | $15,387 | $105,500 |
$15,387
303,048
kWh
|
|
04 | 2.2511: Insulate bare equipment | $1,728 | $1,880 |
$1,728
53,048
kWh
|
|
05 | 2.4133: Use most efficient type of electric motors | $1,060 | $9,500 |
$1,060
24,033
kWh
|
|
TOTAL RECOMMENDED | $27,094 | $126,880 |
$27,094
417,644
kWh
|
||
TOTAL IMPLEMENTED | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs