Assessment Year | 2000 |
---|---|
Principal Product | Pharmaceutical Tool and Die |
NAICS |
n/a
|
SIC | 3544: Special Dies and Tools, Die Sets, Jigs and Fixtures, and Industrial Molds |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
105,000
ft2
|
Annual Production | 780,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $186,124 | 3,747,069 |
kWh
|
$0.050 |
Electricity Demand | $20,439 | 864 |
kW-mo/yr
|
$23.66 |
Electricity Fees | $14,743 | - |
|
- |
Natural Gas | $11,164 | 2,571 |
MMBtu
|
$4.34 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $88,092 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,744 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,098 | $3,399 |
$2,800
52,169
kWh
|
$298
-
kW-mo/yr
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $7,238 | $9,332 |
$6,545
122,216
kWh
|
$693
-
kW-mo/yr
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,506 | $175 |
$2,265
42,204
kWh
|
$241
-
kW-mo/yr
|
- | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,270 | $825 |
$617
11,430
kWh
|
$653
-
kW-mo/yr
|
- | - | - | |
05 | 3.7198: Reduce / eliminate use of disposable product | $11,232 | $2,160 | - | - |
$11,232
-
lb
|
- | - | |
06 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $2,496 | - | - | - |
$2,496
-
lb
|
- | - | |
07 | 4.445: Install equipment to move product | $58,989 | $7,500 | - | - | - | $58,989 | - | |
08 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,263 | - | - | - | - | - | $1,263 | |
TOTAL RECOMMENDED | $88,092 | $23,391 |
$12,227
228,019
kWh
|
$1,885
-
kW-mo/yr
|
$13,728
-
lb
|
$58,989 | $1,263 | ||
TOTAL IMPLEMENTED | $9,744 | $9,507 |
$8,810
164,420
kWh
|
$934
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs