Assessment Year | 1999 |
---|---|
Principal Product | Indexing Equipment |
NAICS |
n/a
|
SIC | 3549: Metalworking Machinery, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 70 |
Plant Area |
103,400
ft2
|
Annual Production | 321,300
units
|
Production Hrs. Annual | 4,590
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $109,205 | 2,133,646 |
kWh
|
$0.051 |
Electricity Demand | $12,825 | 576 |
kW-mo/yr
|
$22.27 |
Electricity Fees | $14,800 | - |
|
- |
Natural Gas | $18,439 | 3,709 |
MMBtu
|
$4.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $266,631 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,627 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,574 | $10,069 |
$3,151
54,220
kWh
|
$423
-
kW-mo/yr
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $2,533 | $3,290 |
$2,333
40,152
kWh
|
$200
-
kW-mo/yr
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $488 | $60 |
$443
7,620
kWh
|
$45
-
kW-mo/yr
|
- | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $437 | - |
$392
6,741
kWh
|
$45
-
kW-mo/yr
|
- | - | - | |
05 | 4.652: Replace existing equipment with more suitable substitutes | $400 | - | - | - |
$400
-
lb
|
- | - | |
06 | 4.512: Condense operation into one building | $250,000 | $125,000 | - | - | - | - | $250,000 | |
07 | 3.5248: Separate and recycle scrap metal to foundry or for sale | $5,216 | - | - | - | - | $5,216 | - | |
08 | 4.611: Begin a practice of predictive / preventative maintenance | $2,520 | $3,700 | - | - | - | $2,520 | - | |
09 | 2.3134: Shift from daytime to nighttime operation | $1,463 | - | - | - | - | $1,463 | - | |
TOTAL RECOMMENDED | $266,631 | $142,119 |
$6,319
108,733
kWh
|
$713
-
kW-mo/yr
|
$400
-
lb
|
$9,199 | $250,000 | ||
TOTAL IMPLEMENTED | $8,627 | $17,059 |
$5,484
94,372
kWh
|
$623
-
kW-mo/yr
|
- | $2,520 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs