Assessment Year | 1997 |
---|---|
Principal Product | Pillows and Cushions |
NAICS |
n/a
|
SIC | 2392: House furnishing, Except Curtains and Draperies |
Sales Range | $10 M to 50M |
# of Employees | 165 |
Plant Area |
45,000
ft2
|
Annual Production | 3,600,000
pieces
|
Production Hrs. Annual | 2,400
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $31,259 | 682,591 |
kWh
|
$0.046 |
Electricity Demand | $15,405 | 419 |
kW-mo/yr
|
$36.77 |
Electricity Fees | $48,579 | - |
|
- |
LPG | $25,683 | 3,010 |
MMBtu
|
$8.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,882 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,857 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.711: Initiate a total quality management program | $8,647 | $20,000 | - | - | - | $8,647 | |
02 | 4.514: Re-arrange equipment layout to reduce handling costs | $4,050 | $10,000 | - | - | - | $4,050 | |
03 | 4.432: Cross-train personnel to avoid lost time | $1,130 | $3,000 | - | - | - | $1,130 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,985 | $5,340 |
$1,496
30,774
kWh
|
$489
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $994 | $1,896 |
$751
15,533
kWh
|
$243
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $101 | $207 |
$94
2,052
kWh
|
$7
-
kW-mo/yr
|
- | - | |
07 | 2.4131: Size electric motors for peak operating efficiency | $329 | $963 |
$208
4,396
kWh
|
$121
-
kW-mo/yr
|
- | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $993 | $40 |
$750
15,533
kWh
|
$243
-
kW-mo/yr
|
- | - | |
09 | 2.4221: Install compressor air intakes in coolest locations | $606 | $51 |
$459
9,379
kWh
|
$147
-
kW-mo/yr
|
- | - | |
10 | 3.7196: Use re-usable filters | $4,451 | $1,360 | - | - |
$4,451
-
lb
|
- | |
11 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $4,596 | $5,360 | - | - |
$4,596
-
lb
|
- | |
TOTAL RECOMMENDED | $27,882 | $48,217 |
$3,758
77,667
kWh
|
$1,250
-
kW-mo/yr
|
$9,047
-
lb
|
$13,827 | ||
TOTAL IMPLEMENTED | $15,857 | $36,117 |
$1,512
31,360
kWh
|
$518
-
kW-mo/yr
|
- | $13,827 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs