| Assessment Year | 1995 |
|---|---|
| Principal Product | Rubber/steel composite products |
| NAICS |
n/a
|
| SIC | 3061: Molded, Extruded, and Lathe-Cut Mechanical Rubber Goods |
| Sales Range | $10 M to 50M |
| # of Employees | 105 |
| Plant Area |
74,000
ft2
|
| Annual Production | 3,000
lb
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $548,760 | 10,179,074 |
kWh
|
$0.054 |
| Natural Gas | $160,727 | 28,500 |
MMBtu
|
$5.64 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $50,108 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $49,337 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,126 | $2,024 |
$2,126
40,739
kWh
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $997 | $682 |
$997
19,050
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $122 | - |
$122
2,345
kWh
|
- | |
| 04 | 2.4133: Use most efficient type of electric motors | $8,649 | $15,514 |
$8,649
164,713
kWh
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $180 | - |
$180
3,517
kWh
|
- | |
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $771 | $642 |
$771
10,258
kWh
|
- | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $8,440 | $306 |
$8,440
161,489
kWh
|
- | |
| 08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $10,805 | $5,000 |
$10,805
206,624
kWh
|
- | |
| 09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $18,018 | $11,160 |
$30,639
524,619
kWh
|
$(-12,621.0)
-
MMBtu
|
|
| TOTAL RECOMMENDED | $50,108 | $35,328 |
$62,729
1,133,354
kWh
|
$(-12,621.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $49,337 | $34,686 |
$61,958
1,123,096
kWh
|
$(-12,621.0)
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs