| Assessment Year | 1994 |
|---|---|
| Principal Product | Granite Granules |
| NAICS |
n/a
|
| SIC | 3295: Minerals and Earths, Ground or Otherwise Treated |
| Sales Range | $5 M to 10M |
| # of Employees | 144 |
| Plant Area |
80,000
ft2
|
| Annual Production | 450,000
ton
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $662,943 | 12,490,035 |
kWh
|
$0.053 |
| Natural Gas | $822,695 | 311,097 |
MMBtu
|
$2.64 |
| LPG | $2,850 | 490 |
MMBtu
|
$5.82 |
| Fuel Oil #1 | $9,683 | 1,581 |
MMBtu
|
$6.12 |
| Fuel Oil #2 | $53,313 | 9,898 |
MMBtu
|
$5.39 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $32,278 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,468 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $19,322 | $44,473 |
$19,322
364,009
kWh
|
- | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,128 | $670 |
$4,128
77,667
kWh
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $2,101 | $609 |
$2,101
39,566
kWh
|
- | |
| 04 | 2.4314: Use synthetic lubricant | $1,817 | $368 |
$1,817
34,291
kWh
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,698 | $120 |
$1,698
31,946
kWh
|
- | |
| 06 | 2.2437: Recover waste heat from equipment | $883 | $137 | - |
$883
-
MMBtu
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,637 | $6,595 |
$1,637
30,774
kWh
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $692 | $242 |
$692
13,189
kWh
|
- | |
| TOTAL RECOMMENDED | $32,278 | $53,214 |
$31,395
591,442
kWh
|
$883
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $23,468 | $51,678 |
$23,468
442,263
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs