| Assessment Year | 1994 |
|---|---|
| Principal Product | Battery Chargers |
| NAICS |
n/a
|
| SIC | 3629: Electrical Industrial Apparatus, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 190 |
| Plant Area |
230,900
ft2
|
| Annual Production | 320,420
pieces
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $88,558 | 1,143,318 |
kWh
|
$0.077 |
| Natural Gas | $76,000 | 15,662 |
MMBtu
|
$4.85 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $31,967 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $12,118 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7231: Use radiant heater for spot heating | $13,598 | $32,200 | - |
$13,598
-
MMBtu
|
|
| 02 | 2.6121: Reduce hot water temperature to the minimum required | $140 | $80 |
$81
1,172
kWh
|
$59
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,941 | $22,684 |
$4,941
63,892
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,377 | $1,232 |
$3,377
43,669
kWh
|
- | |
| 05 | 2.4133: Use most efficient type of electric motors | $2,882 | $4,863 |
$2,882
37,222
kWh
|
- | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,789 | $350 |
$1,789
23,154
kWh
|
- | |
| 07 | 2.2511: Insulate bare equipment | $1,519 | $2,083 |
$1,519
19,637
kWh
|
- | |
| 08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,310 | $1,806 |
$1,682
17,878
kWh
|
$(-372.0)
-
MMBtu
|
|
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,424 | $40 |
$1,424
18,464
kWh
|
- | |
| 10 | 2.4221: Install compressor air intakes in coolest locations | $987 | $1,093 |
$987
12,896
kWh
|
- | |
| TOTAL RECOMMENDED | $31,967 | $66,431 |
$18,682
237,984
kWh
|
$13,285
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $12,118 | $9,741 |
$12,059
156,214
kWh
|
$59
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs