| Assessment Year | 1992 |
|---|---|
| Principal Product | BUILDING PRODUCTS |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 90 |
| Plant Area |
n/a
|
| Annual Production | 7,900,000
lb
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $259,875 | 4,243,259 |
kWh
|
$0.061 |
| Natural Gas | $2,303 | 515 |
MMBtu
|
$4.47 |
| LPG | $2,794 | 321 |
MMBtu
|
$8.70 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $5,711 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,562 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $1,060 | $8,000 |
$1,060
17,292
kWh
|
|
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,904 | $235 |
$1,904
31,067
kWh
|
|
| 03 | 2.4221: Install compressor air intakes in coolest locations | $1,648 | $760 |
$1,648
26,964
kWh
|
|
| 04 | 2.4131: Size electric motors for peak operating efficiency | $149 | $354 |
$149
2,345
kWh
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $950 | $10,000 |
$950
15,533
kWh
|
|
| TOTAL RECOMMENDED | $5,711 | $19,349 |
$5,711
93,201
kWh
|
||
| TOTAL IMPLEMENTED | $5,562 | $18,995 |
$5,562
90,856
kWh
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs