Assessment Year | 1992 |
---|---|
Principal Product | BUILDING PRODUCTS |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 90 |
Plant Area |
n/a
|
Annual Production | 7,900,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $259,875 | 4,243,259 |
kWh
|
$0.061 |
Natural Gas | $2,303 | 515 |
MMBtu
|
$4.47 |
LPG | $2,794 | 321 |
MMBtu
|
$8.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $5,711 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,562 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $1,060 | $8,000 |
$1,060
17,292
kWh
|
|
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,904 | $235 |
$1,904
31,067
kWh
|
|
03 | 2.4221: Install compressor air intakes in coolest locations | $1,648 | $760 |
$1,648
26,964
kWh
|
|
04 | 2.4131: Size electric motors for peak operating efficiency | $149 | $354 |
$149
2,345
kWh
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $950 | $10,000 |
$950
15,533
kWh
|
|
TOTAL RECOMMENDED | $5,711 | $19,349 |
$5,711
93,201
kWh
|
||
TOTAL IMPLEMENTED | $5,562 | $18,995 |
$5,562
90,856
kWh
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs