| Assessment Year | 2024 |
|---|---|
| Principal Product | IAA Repair/Overhaul of Airplane Engines |
| NAICS | 336411: Aircraft Manufacturing |
| SIC | 3721: Aircraft |
| Sales Range | $10 M to 50M |
| # of Employees | 162 |
| Plant Area |
125,000
ft2
|
| Annual Production | 33,000
pieces
|
| Production Hrs. Annual | 5,151
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $142,292 | 2,410,320 |
kWh
|
$0.059 |
| Electricity Demand | $104,673 | 6,878 |
kW-mo/yr
|
$15.22 |
| Electricity Fees | $63,921 | - |
|
- |
| TOTAL YEARLY COSTS | $310,886 | |||
| RECOMMENDED SAVINGS* | $108,095 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,470 | $860 |
$3,415
57,881
kWh
|
$2,055
-
kW-mo/yr
|
|
| 02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,989 | $960 |
$665
11,279
kWh
|
$1,324
-
kW-mo/yr
|
|
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,550 | $1,660 |
$1,591
26,962
kWh
|
$959
-
kW-mo/yr
|
|
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $6,049 | $4,092 |
$3,781
64,085
kWh
|
$2,268
-
kW-mo/yr
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,650 | $23,081 |
$10,400
176,267
kWh
|
$6,250
-
kW-mo/yr
|
|
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $14,517 | $21,120 |
$9,069
153,704
kWh
|
$5,448
-
kW-mo/yr
|
|
| 07 | 2.7243: Improve air circulation with destratification fans / other methods | $2,069 | $3,165 |
$1,293
21,909
kWh
|
$776
-
kW-mo/yr
|
|
| 08 | 2.7232: Replace existing hvac unit with high efficiency model | $5,068 | $14,019 |
$3,647
61,817
kWh
|
$1,421
-
kW-mo/yr
|
|
| 09 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $204 | $590 |
$128
2,168
kWh
|
$76
-
kW-mo/yr
|
|
| 10 | 2.9114: Use solar heat to make electricty | $53,529 | $245,201 |
$17,606
298,413
kWh
|
$35,923
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $108,095 | $314,748 |
$51,595
874,485
kWh
|
$56,500
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs