Assessment Year | 2023 |
---|---|
Principal Product | Printed material |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 160 |
Plant Area |
96,000
ft2
|
Annual Production | 36,000,000
pieces
|
Production Hrs. Annual | 4,290
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $252,030 | 3,766,835 |
kWh
|
$0.067 |
Electricity Demand | $146,332 | 12,084 |
kW-mo/yr
|
$12.11 |
Electricity Fees | $70,540 | - |
|
- |
TOTAL YEARLY COSTS | $468,902 | |||
RECOMMENDED SAVINGS* | $89,998 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $56,597 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $31,593 | - |
$31,593
471,535
kWh
|
- | |
02 | 2.7232: Replace existing hvac unit with high efficiency model | $12,768 | $62,963 |
$8,481
126,586
kWh
|
$4,287
-
kW-mo/yr
|
|
03 | 2.7442: Keep doors and windows shut when not on use | $11,974 | - |
$7,953
118,699
kWh
|
$4,021
-
kW-mo/yr
|
|
04 | 2.7221: Lower temperature during the winter season and vice-versa | $7,404 | $630 |
$5,939
88,638
kWh
|
$1,465
-
kW-mo/yr
|
|
05 | 2.7229: Air condition only space necessary | $5,093 | $4,315 |
$3,524
52,604
kWh
|
$1,569
-
kW-mo/yr
|
|
06 | 2.7273: Install desiccant humidity control system | $4,219 | $12,866 |
$3,383
50,493
kWh
|
$836
-
kW-mo/yr
|
|
07 | 2.2312: Minimize non-essential material in heat treatment process | $3,449 | $1,600 |
$3,449
51,480
kWh
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,373 | $2,640 |
$2,259
33,711
kWh
|
$1,114
-
kW-mo/yr
|
|
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,177 | $1,660 |
$1,693
25,268
kWh
|
$484
-
kW-mo/yr
|
|
10 | 2.7135: Install occupancy sensors | $2,010 | $1,344 |
$2,010
29,995
kWh
|
- | |
11 | 2.7444: Close holes and openings in building such as broken windows | $1,774 | $205 |
$1,178
17,588
kWh
|
$596
-
kW-mo/yr
|
|
12 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,713 | $6,180 |
$1,138
16,989
kWh
|
$575
-
kW-mo/yr
|
|
13 | 2.4239: Eliminate or reduce compressed air usage | $1,450 | $2,090 |
$1,123
16,768
kWh
|
$327
-
kW-mo/yr
|
|
14 | 2.7424: Shade windows from summer sun | $1,001 | $1,664 |
$662
9,880
kWh
|
$339
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $89,998 | $98,157 |
$74,385
1,110,234
kWh
|
$15,613
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $56,597 | $3,890 |
$50,627
755,620
kWh
|
$5,970
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs