Assessment Year 2008
Principal Product fiber drums
NAICS 322219: Other Paperboard Container Manufacturing
SIC 2655: Fiber Cans, Tubes, Drums, and Similar Products
Sales Range $10
M
to 50
M
# of Employees 69
Plant Area 128,000
ft2
Annual Production 1,218,097
pieces
Production Hrs. Annual 3,990
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $176,644 1,095,900
kWh
Electricity Fees $315 -
Natural Gas $40,929 3,650
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $121,067 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $25,007

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $15,195 - $15,195
85,189
kWh
02 2.7134: Use photocell controls $1,238 $786 $1,238
6,943
kWh
03 2.7135: Install occupancy sensors $666 $584 $666
3,734
kWh
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $2,838 $2,773 $2,838
15,908
kWh
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $146 $200 $146
821
kWh
06 2.7134: Use photocell controls $1,435 $2,319 $1,435
6,971
kWh
07 2.4133: Use most efficient type of electric motors $781 $1,851 $781
4,379
kWh
08 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $9,812 $56,073 $9,812
55,012
kWh
09 2.9114: Use solar heat to make electricty $88,956 $1,020,250 $88,956
498,717
kWh
TOTAL RECOMMENDED $121,067 $1,084,836 $121,067
677,674
kWh
TOTAL IMPLEMENTED $25,007 $56,073 $25,007
140,201
kWh
Yearly Savings* Imp'd Cost* Electricity Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs