ITAC Assessment: MI0413
ITAC logo
ITAC Assessment: MI0413
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2023
Principal Product Electronics
NAICS 334419: Other Electronic Component Manufacturing
SIC 3679: Electronic Components, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 91,000
ft2
Annual Production 80,000,000
units
Production Hrs. Annual 4,212
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $49,447 813,360
kWh
Electricity Demand $26,553 2,259
kW-mo/yr
Electricity Fees $12,991 -
Natural Gas $12,000 1,334
MMBtu
TOTAL YEARLY COSTS $100,991
RECOMMENDED SAVINGS* $20,210 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $12,273

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.7496: Install partitions to reduce size of conditioned space $7,040 $10,116 $5,570
91,315
kWh
$1,470
-
kW-mo/yr
-
02 2.6218: Turn off equipment when not in use $4,023 - $5,303
86,935
kWh
- $(-1,280.0)
03 2.7142: Utilize higher efficiency lamps and/or ballasts $3,013 $5,249 $1,132
18,557
kWh
$1,881
-
kW-mo/yr
-
04 2.7221: Lower temperature during the winter season and vice-versa $2,034 $580 $964
15,810
kWh
$1,070
-
kW-mo/yr
-
05 2.4235: Remove or close off unneeded compressed air lines $1,089 $5,264 $689
11,300
kWh
$400
-
kW-mo/yr
-
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,004 $1,980 $687
11,255
kWh
$317
-
kW-mo/yr
-
07 2.7447: Install vinyl strip / high speed / air curtain doors $897 $2,750 $580
9,505
kWh
$317
-
kW-mo/yr
-
08 2.7243: Improve air circulation with destratification fans / other methods $755 $645 $596
9,833
kWh
$159
-
kW-mo/yr
-
09 2.7135: Install occupancy sensors $355 $140 $355
5,812
kWh
- -
TOTAL RECOMMENDED $20,210 $26,724 $15,876
260,321
kWh
$5,614
-
kW-mo/yr
$(-1,280.0)
TOTAL IMPLEMENTED $12,273 $13,858 $9,726
159,501
kWh
$3,827
-
kW-mo/yr
$(-1,280.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs