Assessment Year | 2021 |
---|---|
Principal Product | Valve Manufacturing |
NAICS | 332911: Industrial Valve Manufacturing |
SIC | 3491: Industrial Valves |
Sales Range | $1 M to 5M |
# of Employees | 106 |
Plant Area |
38,000
ft2
|
Annual Production | 30,000
pieces
|
Production Hrs. Annual | 4,500
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,712 | 987,120 |
kWh
|
$0.044 |
Electricity Demand | $36,128 | 3,217 |
kW-mo/yr
|
$11.23 |
Electricity Fees | $16,104 | - |
|
- |
Fuel Oil #2 | $5,358 | 275 |
MMBtu
|
$19.48 |
TOTAL YEARLY COSTS | $101,302 | |||
RECOMMENDED SAVINGS* | $35,865 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,646 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7229: Air condition only space necessary | $12,419 | $16,940 |
$9,196
208,998
kWh
|
$3,223
-
kW-mo/yr
|
|
02 | 2.4224: Upgrade controls on compressors | $4,326 | $10,320 |
$3,169
72,024
kWh
|
$1,157
-
kW-mo/yr
|
|
03 | 2.4133: Use most efficient type of electric motors | $3,862 | $9,016 |
$2,222
50,504
kWh
|
$1,640
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,993 | $4,308 |
$1,791
40,706
kWh
|
$1,202
-
kW-mo/yr
|
|
05 | 2.7425: Clean or color roof to reduce solar load | $2,971 | $11,975 |
$1,455
33,068
kWh
|
$1,516
-
kW-mo/yr
|
|
06 | 2.4239: Eliminate or reduce compressed air usage | $1,824 | $120 |
$1,352
30,724
kWh
|
$472
-
kW-mo/yr
|
|
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,595 | $1,980 |
$1,179
26,784
kWh
|
$416
-
kW-mo/yr
|
|
08 | 2.4112: Install soft-start to eliminate nuisance trips | $3,060 | $2,791 |
$1,544
35,097
kWh
|
$1,516
-
kW-mo/yr
|
|
09 | 2.7135: Install occupancy sensors | $1,412 | $780 |
$1,412
32,094
kWh
|
- | |
10 | 2.4323: Use optimum size and capacity equipment | $1,403 | $4,900 |
$1,044
23,716
kWh
|
$359
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $35,865 | $63,130 |
$24,364
553,715
kWh
|
$11,501
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $21,646 | $29,028 |
$15,974
363,022
kWh
|
$5,672
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs