Assessment Year | 2021 |
---|---|
Principal Product | Medical Devices |
NAICS | 339112: Surgical and Medical Instrument Manufacturing |
SIC | 3841: Surgical and Medical Instruments and Apparatus |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
26,000
ft2
|
Annual Production | 5,300,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $266,631 | 1,554,089 |
kWh
|
$0.17 |
Electricity Demand | $25,500 | 2,838 |
kW-mo/yr
|
$8.99 |
Electricity Fees | $2,618 | - |
|
- |
TOTAL YEARLY COSTS | $294,749 | |||
RECOMMENDED SAVINGS* | $39,486 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,675 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,589 | $6,672 |
$12,529
73,058
kWh
|
$1,060
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,047 | $1,660 |
$6,573
38,328
kWh
|
$474
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,898 | $2,100 |
$6,296
36,709
kWh
|
$602
-
kW-mo/yr
|
- | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,719 | $3,215 |
$5,333
31,096
kWh
|
$386
-
kW-mo/yr
|
- | |
05 | 2.8114: Change rate schedules or other changes in utility service | $2,338 | $100 | - | - | $2,338 | |
06 | 2.4238: Do not use compressed air for personal cooling | $1,866 | $4,760 |
$1,736
10,122
kWh
|
$130
-
kW-mo/yr
|
- | |
07 | 2.6127: Maintain air filters by cleaning or replacement | $1,275 | $234 |
$1,109
6,468
kWh
|
$166
-
kW-mo/yr
|
- | |
08 | 2.2511: Insulate bare equipment | $754 | $1,614 |
$616
3,592
kWh
|
$138
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $39,486 | $20,355 |
$34,192
199,373
kWh
|
$2,956
-
kW-mo/yr
|
$2,338 | ||
TOTAL IMPLEMENTED | $30,675 | $15,426 |
$28,243
164,685
kWh
|
$2,432
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs