| Assessment Year | 2019 |
|---|---|
| Principal Product | Turnovers & empanadillas |
| NAICS | 311412: Frozen Specialty Food Manufacturing |
| SIC | 2038: Frozen Specialties, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
30,000
ft2
|
| Annual Production | 7,000,000
pieces
|
| Production Hrs. Annual | 5,460
hrs
|
| Location (State) | Puerto Rico |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $471,566 | 2,462,518 |
kWh
|
$0.19 |
| Electricity Demand | $46,702 | 4,852 |
kW-mo/yr
|
$9.63 |
| Electricity Fees | $5,242 | - |
|
- |
| LPG | $6,558 | 1,118 |
MMBtu
|
$5.87 |
| Fuel Oil #2 | $229,162 | 10,497 |
MMBtu
|
$21.83 |
| TOTAL YEARLY COSTS | $759,230 | |||
| RECOMMENDED SAVINGS* | $100,945 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $65,879 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.9112: Use solar heat to heat water | $36,147 | $40,234 |
$36,147
189,249
kWh
|
- | - | - | |
| 02 | 2.8223: Add air shields to trucks to increase fuel mileage | $34,382 | $15,720 | - | - | - |
$34,382
-
MMBtu
|
|
| 03 | 2.6218: Turn off equipment when not in use | $9,735 | $3,600 |
$9,735
50,970
kWh
|
- | - | - | |
| 04 | 2.3212: Optimize plant power factor | $5,613 | $13,630 | - | - | $5,613 | - | |
| 05 | 2.4133: Use most efficient type of electric motors | $4,707 | $3,634 |
$4,024
21,068
kWh
|
$683
-
kW-mo/yr
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,330 | $3,023 |
$3,993
20,904
kWh
|
$337
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,445 | $1,980 |
$2,243
11,745
kWh
|
$202
-
kW-mo/yr
|
- | - | |
| 08 | 2.7496: Install partitions to reduce size of conditioned space | $1,675 | $3,764 |
$1,569
8,216
kWh
|
$106
-
kW-mo/yr
|
- | - | |
| 09 | 2.7135: Install occupancy sensors | $751 | $211 |
$751
3,932
kWh
|
- | - | - | |
| 10 | 2.8114: Change rate schedules or other changes in utility service | $684 | $100 | - | - | $684 | - | |
| 11 | 2.7444: Close holes and openings in building such as broken windows | $476 | $868 |
$447
2,339
kWh
|
$29
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $100,945 | $86,764 |
$58,909
308,423
kWh
|
$1,357
-
kW-mo/yr
|
$6,297 |
$34,382
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $65,879 | $70,944 |
$58,909
308,423
kWh
|
$1,357
-
kW-mo/yr
|
$5,613 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs