Assessment Year | 2019 |
---|---|
Principal Product | Ophthalmic Lenses |
NAICS | 339115: Ophthalmic Goods Manufacturing |
SIC | 3851: Ophthalmic Goods |
Sales Range | $5 M to 10M |
# of Employees | 64 |
Plant Area |
15,000
ft2
|
Annual Production | 158,000
pieces
|
Production Hrs. Annual | 3,744
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $136,173 | 691,020 |
kWh
|
$0.20 |
Electricity Demand | $20,720 | 2,073 |
kW-mo/yr
|
$10.00 |
Electricity Fees | $(-5,560.0) | - |
|
- |
LPG | $7,116 | 260 |
MMBtu
|
$27.37 |
TOTAL YEARLY COSTS | $158,449 | |||
RECOMMENDED SAVINGS* | $52,415 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $50,319 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $15,430 | $10,964 |
$13,391
67,975
kWh
|
$2,039
-
kW-mo/yr
|
- | - | |
02 | 2.6218: Turn off equipment when not in use | $11,207 | $3,600 |
$11,207
56,888
kWh
|
- | - | - | |
03 | 2.9112: Use solar heat to heat water | $7,116 | $10,125 | - | - | - |
$7,116
-
MMBtu
|
|
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $6,201 | $7,920 |
$5,301
26,908
kWh
|
$900
-
kW-mo/yr
|
- | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,725 | $2,284 |
$3,205
16,271
kWh
|
$520
-
kW-mo/yr
|
- | - | |
06 | 2.8114: Change rate schedules or other changes in utility service | $3,012 | $100 | - | - | $3,012 | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,851 | $1,846 |
$1,591
8,076
kWh
|
$260
-
kW-mo/yr
|
- | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,571 | $1,995 |
$1,351
6,859
kWh
|
$220
-
kW-mo/yr
|
- | - | |
09 | 2.7135: Install occupancy sensors | $656 | $319 |
$566
2,872
kWh
|
$90
-
kW-mo/yr
|
- | - | |
10 | 2.7492: Use proper thickness of insulation on building envelope | $603 | $2,315 |
$403
2,044
kWh
|
$200
-
kW-mo/yr
|
- | - | |
11 | 2.4231: Reduce the pressure of compressed air to the minimum required | $525 | $160 |
$455
2,309
kWh
|
$70
-
kW-mo/yr
|
- | - | |
12 | 2.4323: Use optimum size and capacity equipment | $518 | $2,294 |
$448
2,275
kWh
|
$70
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $52,415 | $43,922 |
$37,918
192,477
kWh
|
$4,369
-
kW-mo/yr
|
$3,012 |
$7,116
-
MMBtu
|
||
TOTAL IMPLEMENTED | $50,319 | $41,767 |
$36,112
183,309
kWh
|
$4,079
-
kW-mo/yr
|
$3,012 |
$7,116
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs