Assessment Year | 2018 |
---|---|
Principal Product | Paints |
NAICS | 325510: Paint and Coating Manufacturing |
SIC | 2851: Paints, Varnishes, Lacquers, Enamels, and Allied Products |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
100,000
ft2
|
Annual Production | 1,300
Tgal
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $33,105 | 510,720 |
kWh
|
$0.065 | |
Electricity Demand | $24,077 | 3,010 |
kW-mo/yr
|
$8.00 | |
Electricity Fees | $6,364 | - |
|
- | |
LPG | $38,427 | 1,021 |
MMBtu
|
$37.64 | |
Waste Disposal Costs | |||||
Water Usage | $16,545 | 2,676 |
Tgal
|
$6.18 | |
TOTAL YEARLY COSTS | $118,517 | ||||
RECOMMENDED SAVINGS* | $24,905 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $13,043 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,234 | $12,519 |
$4,338
66,744
kWh
|
$2,896
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,575 | $13,838 |
$2,735
42,083
kWh
|
$1,840
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,178 | $2,030 |
$1,387
21,343
kWh
|
$791
-
kW-mo/yr
|
- | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $2,175 | $6,578 |
$1,271
19,551
kWh
|
$904
-
kW-mo/yr
|
- | - | |
05 | 2.6218: Turn off equipment when not in use | $1,877 | $1,300 |
$1,877
28,870
kWh
|
- | - | - | |
06 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,637 | $3,750 |
$981
15,099
kWh
|
$656
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,564 | $3,102 |
$1,564
24,068
kWh
|
- | - | - | |
08 | 2.8212: Reduce delivery schedules | $1,454 | $2,490 | - | - | - | $1,454 | |
09 | 2.2414: Use waste heat from hot flue gases to preheat | $816 | $1,980 | - | - |
$816
-
MMBtu
|
- | |
10 | 2.1233: Analyze flue gas for proper air/fuel ratio | $803 | $1,560 | - | - |
$803
-
MMBtu
|
- | |
11 | 2.4221: Install compressor air intakes in coolest locations | $592 | $1,973 |
$355
5,459
kWh
|
$237
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $24,905 | $51,120 |
$14,508
223,217
kWh
|
$7,324
-
kW-mo/yr
|
$1,619
-
MMBtu
|
$1,454 | ||
TOTAL IMPLEMENTED | $13,043 | $26,293 |
$7,918
121,823
kWh
|
$2,868
-
kW-mo/yr
|
$803
-
MMBtu
|
$1,454 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs