Assessment Year | 2017 |
---|---|
Principal Product | Surgical tools |
NAICS | 339112: Surgical and Medical Instrument Manufacturing |
SIC | 3841: Surgical and Medical Instruments and Apparatus |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
66,000
ft2
|
Annual Production | 84,000,000
units
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $581,299 | 3,689,275 |
kWh
|
$0.16 |
Electricity Demand | $82,454 | 10,572 |
kW-mo/yr
|
$7.80 |
Electricity Fees | $8,090 | - |
|
- |
TOTAL YEARLY COSTS | $671,843 | |||
RECOMMENDED SAVINGS* | $182,536 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $78,765 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $94,097 | $134,000 |
$83,336
527,446
kWh
|
$5,761
-
kW-mo/yr
|
- | $5,000 | |
02 | 2.7425: Clean or color roof to reduce solar load | $28,637 | $15,056 |
$26,785
169,528
kWh
|
$1,852
-
kW-mo/yr
|
- | - | |
03 | 2.3212: Optimize plant power factor | $28,032 | $41,300 | - |
$28,032
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,387 | $8,923 |
$7,856
49,722
kWh
|
$531
-
kW-mo/yr
|
- | - | |
05 | 2.8112: Combine utility meters | $7,245 | $100 | - |
$4,845
-
kW-mo/yr
|
$2,400 | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,467 | $4,900 |
$5,467
34,602
kWh
|
- | - | - | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,663 | $1,478 |
$3,430
21,706
kWh
|
$233
-
kW-mo/yr
|
- | - | |
08 | 2.7135: Install occupancy sensors | $3,528 | $1,000 |
$3,528
22,327
kWh
|
- | - | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,760 | $250 |
$1,645
10,410
kWh
|
$115
-
kW-mo/yr
|
- | - | |
10 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,051 | $1,722 |
$983
6,221
kWh
|
$68
-
kW-mo/yr
|
- | - | |
11 | 2.3191: Use demand controller or load shedder | $670 | $100 | - | - | $670 | - | |
TOTAL RECOMMENDED | $182,536 | $208,829 |
$133,030
841,962
kWh
|
$41,437
-
kW-mo/yr
|
$3,070 | $5,000 | ||
TOTAL IMPLEMENTED | $78,765 | $74,379 |
$48,049
304,106
kWh
|
$30,716
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs