| Assessment Year | 2017 |
|---|---|
| Principal Product | Carbonated Beverages |
| NAICS | 312111: Soft Drink Manufacturing |
| SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
| Sales Range | $10 M to 50M |
| # of Employees | 160 |
| Plant Area |
250,000
ft2
|
| Annual Production | 60,000,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $690,105 | 10,895,044 |
kWh
|
$0.063 |
| Electricity Demand | $274,191 | 24,578 |
kW-mo/yr
|
$11.16 |
| Electricity Fees | $83,973 | - |
|
- |
| TOTAL YEARLY COSTS | $1,048,269 | |||
| RECOMMENDED SAVINGS* | $496,037 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $159,716 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2696: Use excess cold process fluid for industrial cooling needs | $313,428 | $142,400 |
$252,438
4,006,947
kWh
|
$60,990
-
kW-mo/yr
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $72,034 | $39,216 |
$58,017
920,907
kWh
|
$14,017
-
kW-mo/yr
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,854 | $61,030 |
$20,018
317,746
kWh
|
$4,836
-
kW-mo/yr
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $21,732 | $1,660 |
$13,422
213,050
kWh
|
$8,310
-
kW-mo/yr
|
|
| 05 | 2.7221: Lower temperature during the winter season and vice-versa | $14,995 | $120 |
$14,995
238,019
kWh
|
- | |
| 06 | 2.7135: Install occupancy sensors | $10,816 | $7,881 |
$10,816
171,697
kWh
|
- | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,887 | $4,577 |
$7,959
126,341
kWh
|
$1,928
-
kW-mo/yr
|
|
| 08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $8,115 | $18,100 |
$4,347
68,990
kWh
|
$3,768
-
kW-mo/yr
|
|
| 09 | 2.4239: Eliminate or reduce compressed air usage | $7,991 | $2,140 |
$6,395
101,503
kWh
|
$1,596
-
kW-mo/yr
|
|
| 10 | 2.7134: Use photocell controls | $4,891 | $4,136 |
$4,891
77,638
kWh
|
- | |
| 11 | 2.7135: Install occupancy sensors | $4,454 | $1,280 |
$4,454
70,699
kWh
|
- | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,829 | $4,674 |
$1,229
19,505
kWh
|
$600
-
kW-mo/yr
|
|
| 13 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,011 | $654 |
$815
12,933
kWh
|
$196
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $496,037 | $287,868 |
$399,796
6,345,975
kWh
|
$96,241
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $159,716 | $118,655 |
$130,161
2,066,059
kWh
|
$29,555
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs