Assessment Year | 2017 |
---|---|
Principal Product | Printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 95 |
Plant Area |
94,000
ft2
|
Annual Production | 100,000,000
units
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $146,917 | 3,041,204 |
kWh
|
$0.048 |
Electricity Demand | $84,184 | 8,036 |
kW-mo/yr
|
$10.48 |
Electricity Fees | $50,109 | - |
|
- |
TOTAL YEARLY COSTS | $281,209 | |||
RECOMMENDED SAVINGS* | $151,811 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $65,814 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $66,228 | $330,000 |
$40,567
845,152
kWh
|
$24,011
-
kW-mo/yr
|
- | $1,650 | |
02 | 2.6218: Turn off equipment when not in use | $26,938 | $3,600 |
$26,938
561,210
kWh
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,634 | $87,759 |
$7,588
158,087
kWh
|
$8,046
-
kW-mo/yr
|
- | - | |
04 | 2.7221: Lower temperature during the winter season and vice-versa | $14,676 | $640 |
$9,137
190,350
kWh
|
$5,539
-
kW-mo/yr
|
- | - | |
05 | 2.8114: Change rate schedules or other changes in utility service | $9,210 | $2,400 | - | - | $9,210 | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,522 | $1,660 |
$2,417
50,361
kWh
|
$3,105
-
kW-mo/yr
|
- | - | |
07 | 2.3132: Recharge batteries on during off-peak demand periods | $3,771 | $3,140 | - |
$3,771
-
kW-mo/yr
|
- | - | |
08 | 2.8123: Pay utility bills on time | $2,996 | - | - | - | $2,996 | - | |
09 | 2.7293: Install dry sprinkler system or other method to reduce heating requirements | $1,743 | $1,756 |
$1,093
22,778
kWh
|
$650
-
kW-mo/yr
|
- | - | |
10 | 2.7135: Install occupancy sensors | $1,537 | $5,036 |
$1,537
32,033
kWh
|
- | - | - | |
11 | 2.4221: Install compressor air intakes in coolest locations | $1,321 | $1,310 |
$829
17,271
kWh
|
$492
-
kW-mo/yr
|
- | - | |
12 | 2.4323: Use optimum size and capacity equipment | $1,128 | $2,500 |
$227
4,736
kWh
|
$901
-
kW-mo/yr
|
- | - | |
13 | 2.4239: Eliminate or reduce compressed air usage | $1,107 | $1,700 |
$478
9,952
kWh
|
$629
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $151,811 | $441,501 |
$90,811
1,891,930
kWh
|
$47,145
-
kW-mo/yr
|
$12,206 | $1,650 | ||
TOTAL IMPLEMENTED | $65,814 | $100,315 |
$38,036
792,436
kWh
|
$15,572
-
kW-mo/yr
|
$12,206 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs