Assessment Year 2016
Principal Product Stainless Steel Pipe
NAICS 331210: Iron and Steel Pipe and Tube Manufacturing from Purchased Steel
SIC 3317: Steel Pipe and Tubes
Sales Range $10
M
to 50
M
# of Employees 74
Plant Area 200,000
ft2
Annual Production 6,000
ton
Production Hrs. Annual 4,000
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $270,644 4,786,200
kWh
Electricity Demand $207,107 19,374
kW-mo/yr
Electricity Fees $48,517 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $98,094 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $59,343

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
01 2.3131: Reschedule plant operations or reduce load to avoid peaks $23,090 $560 - $23,090
-
kW-mo/yr
-
02 2.6218: Turn off equipment when not in use $17,090 $208 $17,090
299,829
kWh
- -
03 2.4231: Reduce the pressure of compressed air to the minimum required $14,550 $40 $12,123
212,688
kWh
$2,427
-
kW-mo/yr
-
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $13,501 $21,680 $8,637
151,525
kWh
$4,864
-
kW-mo/yr
-
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,548 $1,660 $10,791
189,308
kWh
$757
-
kW-mo/yr
-
06 2.7425: Clean or color roof to reduce solar load $9,937 $4,464 $6,359
111,566
kWh
$3,578
-
kW-mo/yr
-
07 2.4239: Eliminate or reduce compressed air usage $3,576 $2,520 $2,293
40,227
kWh
$1,283
-
kW-mo/yr
-
08 2.7134: Use photocell controls $1,616 $2,240 $1,616
28,355
kWh
- -
09 3.4151: Minimize water usage $970 $2,200 - - $970
-
Tgal
10 2.7221: Lower temperature during the winter season and vice-versa $926 $40 $926
16,235
kWh
- -
11 2.7111: Reduce illumination to minimum necessary levels $746 $440 $393
6,902
kWh
$353
-
kW-mo/yr
-
12 2.7447: Install vinyl strip / high speed / air curtain doors $544 $2,357 $202
3,542
kWh
$342
-
kW-mo/yr
-
TOTAL RECOMMENDED $98,094 $38,409 $60,430
1,060,177
kWh
$36,694
-
kW-mo/yr
$970
-
Tgal
TOTAL IMPLEMENTED $59,343 $11,572 $49,975
876,755
kWh
$8,398
-
kW-mo/yr
$970
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs