| Assessment Year | 2015 |
|---|---|
| Principal Product | Bottled Juice |
| NAICS | 311421: Fruit and Vegetable Canning |
| SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
| Sales Range | $10 M to 50M |
| # of Employees | 80 |
| Plant Area |
40,000
ft2
|
| Annual Production | 3,380
Tgal
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $80,698 | 1,512,452 |
kWh
|
$0.053 |
| Electricity Demand | $48,492 | 4,413 |
kW-mo/yr
|
$10.99 |
| Electricity Fees | $23,744 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $44,442 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,937 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3192: Use fossil fuel powered generator during peak demand periods | $15,717 | $1,400 | - | - | $15,717 | |
| 02 | 2.7425: Clean or color roof to reduce solar load | $10,892 | $10,800 |
$8,475
159,908
kWh
|
$2,417
-
kW-mo/yr
|
- | |
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $6,014 | $4,218 |
$4,684
90,215
kWh
|
$1,330
-
kW-mo/yr
|
- | |
| 04 | 2.7496: Install partitions to reduce size of conditioned space | $5,439 | $160 |
$5,439
102,630
kWh
|
- | - | |
| 05 | 2.2515: Use optimum thickness insulation | $2,395 | $8,535 |
$1,091
20,580
kWh
|
$1,304
-
kW-mo/yr
|
- | |
| 06 | 2.3132: Recharge batteries on during off-peak demand periods | $1,450 | $3,140 | - |
$1,450
-
kW-mo/yr
|
- | |
| 07 | 2.8114: Change rate schedules or other changes in utility service | $1,047 | $280 | - | - | $1,047 | |
| 08 | 2.7496: Install partitions to reduce size of conditioned space | $907 | $336 |
$907
17,105
kWh
|
- | - | |
| 09 | 2.7135: Install occupancy sensors | $397 | $709 |
$397
7,492
kWh
|
- | - | |
| 10 | 2.7134: Use photocell controls | $184 | $600 |
$184
3,462
kWh
|
- | - | |
| TOTAL RECOMMENDED | $44,442 | $30,178 |
$21,177
401,392
kWh
|
$6,501
-
kW-mo/yr
|
$16,764 | ||
| TOTAL IMPLEMENTED | $18,937 | $19,467 |
$13,740
261,077
kWh
|
$5,197
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs