Assessment Year | 2015 |
---|---|
Principal Product | Printed Circuit Boards |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $50 M to 100M |
# of Employees | 462 |
Plant Area |
67,000
ft2
|
Annual Production | 300,000
units
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $493,327 | 7,462,700 |
kWh
|
$0.066 |
Electricity Demand | $165,203 | 16,360 |
kW-mo/yr
|
$10.10 |
Electricity Fees | $104,312 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $178,250 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $44,562 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $75,489 | $140,000 |
$46,020
696,219
kWh
|
$11,269
-
kW-mo/yr
|
$18,200 | |
02 | 2.7292: Lower ceiling to reduce conditioned space | $54,079 | $166,590 |
$43,446
657,270
kWh
|
$10,633
-
kW-mo/yr
|
- | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $20,030 | $160 |
$16,091
243,433
kWh
|
$3,939
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,361 | $1,660 |
$13,502
204,260
kWh
|
$4,859
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,483 | $9,820 |
$5,483
83,089
kWh
|
- | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $2,494 | $1,400 |
$1,999
30,287
kWh
|
$495
-
kW-mo/yr
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $942 | $40 |
$619
9,372
kWh
|
$323
-
kW-mo/yr
|
- | |
08 | 2.4221: Install compressor air intakes in coolest locations | $688 | $639 |
$553
8,369
kWh
|
$135
-
kW-mo/yr
|
- | |
09 | 2.7135: Install occupancy sensors | $684 | $177 |
$684
10,356
kWh
|
- | - | |
TOTAL RECOMMENDED | $178,250 | $320,486 |
$128,397
1,942,655
kWh
|
$31,653
-
kW-mo/yr
|
$18,200 | ||
TOTAL IMPLEMENTED | $44,562 | $12,279 |
$35,629
539,151
kWh
|
$8,933
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs