Assessment Year | 2015 |
---|---|
Principal Product | Folding Box Printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
85,000
ft2
|
Annual Production | 230,000,000
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $99,170 | 1,985,040 |
kWh
|
$0.050 |
Electricity Demand | $81,520 | 6,426 |
kW-mo/yr
|
$12.69 |
Electricity Fees | $31,804 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,259 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $72,051 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $26,495 | $1,660 |
$18,502
370,033
kWh
|
$7,993
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $20,275 | $240 |
$19,311
386,219
kWh
|
$964
-
kW-mo/yr
|
- | |
03 | 2.7425: Clean or color roof to reduce solar load | $9,053 | $24,488 |
$5,247
104,946
kWh
|
$3,806
-
kW-mo/yr
|
- | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $8,952 | $2,400 |
$5,169
103,380
kWh
|
$3,783
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,141 | $1,020 |
$3,077
61,418
kWh
|
$1,064
-
kW-mo/yr
|
- | |
06 | 2.7496: Install partitions to reduce size of conditioned space | $3,624 | $4,636 |
$2,687
53,742
kWh
|
$937
-
kW-mo/yr
|
- | |
07 | 2.8114: Change rate schedules or other changes in utility service | $2,067 | $280 | - | - | $2,067 | |
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,686 | $2,295 |
$961
19,212
kWh
|
$725
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,426 | $6,760 |
$1,426
28,470
kWh
|
- | - | |
10 | 2.7221: Lower temperature during the winter season and vice-versa | $391 | $40 |
$391
7,824
kWh
|
- | - | |
11 | 2.4239: Eliminate or reduce compressed air usage | $149 | $346 |
$86
1,713
kWh
|
$63
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $78,259 | $44,165 |
$56,857
1,136,957
kWh
|
$19,335
-
kW-mo/yr
|
$2,067 | ||
TOTAL IMPLEMENTED | $72,051 | $42,865 |
$53,780
1,075,539
kWh
|
$18,271
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs