Assessment Year | 2015 |
---|---|
Principal Product | Newspapers |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $50 M to 100M |
# of Employees | 470 |
Plant Area |
130,000
ft2
|
Annual Production | 25,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $524,366 | 14,238,000 |
kWh
|
$0.037 |
Electricity Demand | $482,465 | 38,461 |
kW-mo/yr
|
$12.54 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $100,919 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,563 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7425: Clean or color roof to reduce solar load | $36,507 | $57,817 |
$18,895
510,668
kWh
|
$17,612
-
kW-mo/yr
|
- | - | |
02 | 2.7447: Install vinyl strip / high speed / air curtain doors | $8,849 | $480 |
$6,039
163,217
kWh
|
$2,810
-
kW-mo/yr
|
- | - | |
03 | 3.4151: Minimize water usage | $8,287 | $16,600 | - | - |
$8,287
-
Tgal
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,969 | $1,660 |
$4,548
122,914
kWh
|
$2,421
-
kW-mo/yr
|
- | - | |
05 | 2.7135: Install occupancy sensors | $6,933 | $912 |
$6,933
187,387
kWh
|
- | - | - | |
06 | 2.7141: Lower light fixtures in high ceiling areas | $6,562 | $16,470 |
$4,480
121,081
kWh
|
$2,082
-
kW-mo/yr
|
- | - | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $6,447 | $3,660 |
$4,402
118,985
kWh
|
$2,045
-
kW-mo/yr
|
- | - | |
08 | 2.4239: Eliminate or reduce compressed air usage | $6,157 | $11,750 |
$4,200
113,519
kWh
|
$1,957
-
kW-mo/yr
|
- | - | |
09 | 2.3132: Recharge batteries on during off-peak demand periods | $5,843 | $6,280 | - |
$3,751
-
kW-mo/yr
|
- | $2,092 | |
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,759 | $80 |
$2,589
69,965
kWh
|
$2,170
-
kW-mo/yr
|
- | - | |
11 | 2.7134: Use photocell controls | $3,476 | $1,080 |
$3,476
93,694
kWh
|
- | - | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $130 | $375 |
$89
2,400
kWh
|
$41
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $100,919 | $117,164 |
$55,651
1,503,830
kWh
|
$34,889
-
kW-mo/yr
|
$8,287
-
Tgal
|
$2,092 | ||
TOTAL IMPLEMENTED | $49,563 | $26,277 |
$32,276
872,081
kWh
|
$15,195
-
kW-mo/yr
|
- | $2,092 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs