Assessment Year | 2014 |
---|---|
Principal Product | Promotional Material |
NAICS | 339950: Sign Manufacturing |
SIC | 3993: Signs and Advertising Specialties |
Sales Range | $100 M to 500M |
# of Employees | 425 |
Plant Area |
450,000
ft2
|
Annual Production | 125,000,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $360,375 | 8,161,977 |
kWh
|
$0.044 |
Electricity Demand | $240,448 | 18,956 |
kW-mo/yr
|
$12.68 |
Electricity Fees | $150,542 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $528,820 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $139,206 | $330,000 |
$65,877
1,497,203
kWh
|
$30,429
-
kW-mo/yr
|
- | $42,900 | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $70,433 | $80 |
$48,209
1,095,669
kWh
|
$22,224
-
kW-mo/yr
|
- | - | |
03 | 2.7425: Clean or color roof to reduce solar load | $58,931 | $93,833 |
$40,309
916,121
kWh
|
$18,622
-
kW-mo/yr
|
- | - | |
04 | 2.3192: Use fossil fuel powered generator during peak demand periods | $47,940 | $1,400 | - | - | - | $47,940 | |
05 | 2.7496: Install partitions to reduce size of conditioned space | $33,525 | $8,960 |
$22,933
521,212
kWh
|
$10,592
-
kW-mo/yr
|
- | - | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $33,490 | $80 |
$22,910
520,676
kWh
|
$10,580
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $30,776 | $62,320 |
$21,033
478,034
kWh
|
$9,743
-
kW-mo/yr
|
- | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $27,155 | $33,600 |
$27,155
617,162
kWh
|
- | - | - | |
09 | 2.2522: Isolate hot or cold equipment | $22,002 | $26,830 |
$10,433
237,120
kWh
|
$11,569
-
kW-mo/yr
|
- | - | |
10 | 2.7132: Install timers on light switches in little used areas | $18,560 | $640 |
$18,560
422,499
kWh
|
- | - | - | |
11 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,297 | $1,660 |
$3,795
86,240
kWh
|
$7,502
-
kW-mo/yr
|
- | - | |
12 | 3.5313: Increase amount of waste recovered for resale | $7,749 | $800 | - | - | $7,749 | - | |
13 | 2.7111: Reduce illumination to minimum necessary levels | $7,686 | $3,200 |
$5,250
119,329
kWh
|
$2,436
-
kW-mo/yr
|
- | - | |
14 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,659 | $9,784 |
$5,223
118,716
kWh
|
$2,436
-
kW-mo/yr
|
- | - | |
15 | 2.7229: Air condition only space necessary | $5,676 | $20,960 |
$3,849
87,483
kWh
|
$1,827
-
kW-mo/yr
|
- | - | |
16 | 2.4239: Eliminate or reduce compressed air usage | $4,110 | $4,800 |
$2,811
63,891
kWh
|
$1,299
-
kW-mo/yr
|
- | - | |
17 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,625 | $80 |
$1,164
26,445
kWh
|
$1,461
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $528,820 | $599,027 |
$299,511
6,807,800
kWh
|
$130,720
-
kW-mo/yr
|
$7,749 | $90,840 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs