Assessment Year 2014
Principal Product Promotional Material
NAICS 339950: Sign Manufacturing
SIC 3993: Signs and Advertising Specialties
Sales Range $100
M
to 500
M
# of Employees 425
Plant Area 450,000
ft2
Annual Production 125,000,000
pieces
Production Hrs. Annual 7,488
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $360,375 8,161,977
kWh
Electricity Demand $240,448 18,956
kW-mo/yr
Electricity Fees $150,542 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $528,820 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
01 2.2628: Utilize a less expensive cooling method $139,206 $330,000 $65,877
1,497,203
kWh
$30,429
-
kW-mo/yr
- $42,900
02 2.7221: Lower temperature during the winter season and vice-versa $70,433 $80 $48,209
1,095,669
kWh
$22,224
-
kW-mo/yr
- -
03 2.7425: Clean or color roof to reduce solar load $58,931 $93,833 $40,309
916,121
kWh
$18,622
-
kW-mo/yr
- -
04 2.3192: Use fossil fuel powered generator during peak demand periods $47,940 $1,400 - - - $47,940
05 2.7496: Install partitions to reduce size of conditioned space $33,525 $8,960 $22,933
521,212
kWh
$10,592
-
kW-mo/yr
- -
06 2.7221: Lower temperature during the winter season and vice-versa $33,490 $80 $22,910
520,676
kWh
$10,580
-
kW-mo/yr
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $30,776 $62,320 $21,033
478,034
kWh
$9,743
-
kW-mo/yr
- -
08 2.6231: Utilize controls to operate equipment only when needed $27,155 $33,600 $27,155
617,162
kWh
- - -
09 2.2522: Isolate hot or cold equipment $22,002 $26,830 $10,433
237,120
kWh
$11,569
-
kW-mo/yr
- -
10 2.7132: Install timers on light switches in little used areas $18,560 $640 $18,560
422,499
kWh
- - -
11 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,297 $1,660 $3,795
86,240
kWh
$7,502
-
kW-mo/yr
- -
12 3.5313: Increase amount of waste recovered for resale $7,749 $800 - - $7,749 -
13 2.7111: Reduce illumination to minimum necessary levels $7,686 $3,200 $5,250
119,329
kWh
$2,436
-
kW-mo/yr
- -
14 2.7447: Install vinyl strip / high speed / air curtain doors $7,659 $9,784 $5,223
118,716
kWh
$2,436
-
kW-mo/yr
- -
15 2.7229: Air condition only space necessary $5,676 $20,960 $3,849
87,483
kWh
$1,827
-
kW-mo/yr
- -
16 2.4239: Eliminate or reduce compressed air usage $4,110 $4,800 $2,811
63,891
kWh
$1,299
-
kW-mo/yr
- -
17 2.4231: Reduce the pressure of compressed air to the minimum required $2,625 $80 $1,164
26,445
kWh
$1,461
-
kW-mo/yr
- -
TOTAL RECOMMENDED $528,820 $599,027 $299,511
6,807,800
kWh
$130,720
-
kW-mo/yr
$7,749 $90,840
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs