Assessment Year 2014
Principal Product Fresh and Frozen Prepared Fish
NAICS 311710: Seafood Product Preparation and Packaging
SIC 2092: Prepared Fresh or Frozen Fish and Seafoods
Sales Range $10
M
to 50
M
# of Employees 35
Plant Area 40,000
ft2
Annual Production 6,666,667
lb
Production Hrs. Annual 6,916
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $105,162 1,925,526
kWh
Electricity Demand $45,940 4,044
kW-mo/yr
Electricity Fees $35,130 -
Fuel Oil #2 $13,920 745
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $60,328 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $27,594

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Fuel Oil #2 Savings Administrative Changes Savings Water Consumption Savings
01 2.2628: Utilize a less expensive cooling method $18,615 $80,000 $6,048
109,955
kWh
$2,167
-
kW-mo/yr
- $10,400 -
02 2.3192: Use fossil fuel powered generator during peak demand periods $14,962 $2,560 - - - $14,962 -
03 2.7221: Lower temperature during the winter season and vice-versa $5,086 $80 $3,746
68,108
kWh
$1,340
-
kW-mo/yr
- - -
04 2.7425: Clean or color roof to reduce solar load $5,029 $3,340 $3,700
67,280
kWh
$1,329
-
kW-mo/yr
- - -
05 2.7447: Install vinyl strip / high speed / air curtain doors $3,950 $429 $3,077
55,960
kWh
$873
-
kW-mo/yr
- - -
06 2.6218: Turn off equipment when not in use $2,765 $3,600 $2,038
37,060
kWh
$727
-
kW-mo/yr
- - -
07 2.7111: Reduce illumination to minimum necessary levels $2,203 $760 $1,624
29,520
kWh
$579
-
kW-mo/yr
- - -
08 2.7221: Lower temperature during the winter season and vice-versa $2,006 $80 $1,477
26,862
kWh
$529
-
kW-mo/yr
- - -
09 3.4151: Minimize water usage $1,960 $1,930 - - - - $1,960
-
Tgal
10 2.1332: Convert combustion equipment to burn natural gas $1,873 $8,000 - - $1,873
-
MMBtu
- -
11 2.8114: Change rate schedules or other changes in utility service $1,235 $2,100 - - - $1,235 -
12 2.2511: Insulate bare equipment $644 $1,410 $474
8,615
kWh
$170
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $60,328 $104,289 $22,184
403,360
kWh
$7,714
-
kW-mo/yr
$1,873
-
MMBtu
$26,597 $1,960
-
Tgal
TOTAL IMPLEMENTED $27,594 $83,769 $12,825
233,195
kWh
$4,369
-
kW-mo/yr
- $10,400 -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Fuel Oil #2 Savings Administrative Changes Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs