Assessment Year | 2014 |
---|---|
Principal Product | Fresh and Frozen Prepared Fish |
NAICS | 311710: Seafood Product Preparation and Packaging |
SIC | 2092: Prepared Fresh or Frozen Fish and Seafoods |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
40,000
ft2
|
Annual Production | 6,666,667
lb
|
Production Hrs. Annual | 6,916
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $105,162 | 1,925,526 |
kWh
|
$0.055 |
Electricity Demand | $45,940 | 4,044 |
kW-mo/yr
|
$11.36 |
Electricity Fees | $35,130 | - |
|
- |
Fuel Oil #2 | $13,920 | 745 |
MMBtu
|
$18.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $60,328 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,594 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Administrative Changes Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $18,615 | $80,000 |
$6,048
109,955
kWh
|
$2,167
-
kW-mo/yr
|
- | $10,400 | - | |
02 | 2.3192: Use fossil fuel powered generator during peak demand periods | $14,962 | $2,560 | - | - | - | $14,962 | - | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $5,086 | $80 |
$3,746
68,108
kWh
|
$1,340
-
kW-mo/yr
|
- | - | - | |
04 | 2.7425: Clean or color roof to reduce solar load | $5,029 | $3,340 |
$3,700
67,280
kWh
|
$1,329
-
kW-mo/yr
|
- | - | - | |
05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,950 | $429 |
$3,077
55,960
kWh
|
$873
-
kW-mo/yr
|
- | - | - | |
06 | 2.6218: Turn off equipment when not in use | $2,765 | $3,600 |
$2,038
37,060
kWh
|
$727
-
kW-mo/yr
|
- | - | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $2,203 | $760 |
$1,624
29,520
kWh
|
$579
-
kW-mo/yr
|
- | - | - | |
08 | 2.7221: Lower temperature during the winter season and vice-versa | $2,006 | $80 |
$1,477
26,862
kWh
|
$529
-
kW-mo/yr
|
- | - | - | |
09 | 3.4151: Minimize water usage | $1,960 | $1,930 | - | - | - | - |
$1,960
-
Tgal
|
|
10 | 2.1332: Convert combustion equipment to burn natural gas | $1,873 | $8,000 | - | - |
$1,873
-
MMBtu
|
- | - | |
11 | 2.8114: Change rate schedules or other changes in utility service | $1,235 | $2,100 | - | - | - | $1,235 | - | |
12 | 2.2511: Insulate bare equipment | $644 | $1,410 |
$474
8,615
kWh
|
$170
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $60,328 | $104,289 |
$22,184
403,360
kWh
|
$7,714
-
kW-mo/yr
|
$1,873
-
MMBtu
|
$26,597 |
$1,960
-
Tgal
|
||
TOTAL IMPLEMENTED | $27,594 | $83,769 |
$12,825
233,195
kWh
|
$4,369
-
kW-mo/yr
|
- | $10,400 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Administrative Changes Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs