Assessment Year 2014
Principal Product Steel Products
NAICS 325412: Pharmaceutical Preparation Manufacturing
SIC 2834: Pharmaceutical Preparations
Sales Range $10
M
to 50
M
# of Employees 48
Plant Area 94,000
ft2
Annual Production 12,000
ton
Production Hrs. Annual 4,420
hrs
Location (State) Puerto Rico

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $103,693 470,989
kWh
Electricity Demand $34,677 3,001
kW-mo/yr
Electricity Fees $5,400 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $50,716 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $32,916

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.6218: Turn off equipment when not in use $9,165 $1,800 $8,021
36,457
kWh
$1,144
-
kW-mo/yr
02 2.3212: Optimize plant power factor $8,786 $800 - $8,786
-
kW-mo/yr
03 2.7121: Utilize daylight whenever possible in lieu of artificial light $6,657 $40 $5,178
23,536
kWh
$1,479
-
kW-mo/yr
04 2.7145: Install skylights $5,547 $1,340 $4,854
22,065
kWh
$693
-
kW-mo/yr
05 2.7447: Install vinyl strip / high speed / air curtain doors $5,455 $5,293 $4,774
21,704
kWh
$681
-
kW-mo/yr
06 2.7142: Utilize higher efficiency lamps and/or ballasts $4,662 $3,500 $4,084
18,564
kWh
$578
-
kW-mo/yr
07 2.7221: Lower temperature during the winter season and vice-versa $3,969 $80 $3,472
15,781
kWh
$497
-
kW-mo/yr
08 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses $2,136 $1,175 $1,870
8,502
kWh
$266
-
kW-mo/yr
09 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,951 $1,660 $1,771
8,051
kWh
$180
-
kW-mo/yr
10 2.4231: Reduce the pressure of compressed air to the minimum required $1,364 $80 $1,037
4,713
kWh
$327
-
kW-mo/yr
11 2.6127: Maintain air filters by cleaning or replacement $1,024 $347 $897
4,076
kWh
$127
-
kW-mo/yr
TOTAL RECOMMENDED $50,716 $16,115 $35,958
163,449
kWh
$14,758
-
kW-mo/yr
TOTAL IMPLEMENTED $32,916 $4,807 $20,376
92,614
kWh
$12,540
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs