Assessment Year | 2013 |
---|---|
Principal Product | Electronic Circuits |
NAICS | 334419: Other Electronic Component Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 231 |
Plant Area |
100,000
ft2
|
Annual Production | 300,000
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $284,264 | 4,337,539 |
kWh
|
$0.066 |
Electricity Demand | $119,485 | 11,578 |
kW-mo/yr
|
$10.32 |
Electricity Fees | $11,602 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $126,490 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $93,920 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $30,611 | $1,800 |
$20,590
328,130
kWh
|
$10,021
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $26,976 | $407 |
$15,065
240,084
kWh
|
$11,911
-
kW-mo/yr
|
|
03 | 2.7221: Lower temperature during the winter season and vice-versa | $24,698 | $160 |
$18,536
279,448
kWh
|
$6,162
-
kW-mo/yr
|
|
04 | 2.7496: Install partitions to reduce size of conditioned space | $13,325 | $13,200 |
$7,226
115,149
kWh
|
$6,099
-
kW-mo/yr
|
|
05 | 2.7425: Clean or color roof to reduce solar load | $12,407 | $1,680 |
$6,731
107,262
kWh
|
$5,676
-
kW-mo/yr
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,737 | $1,660 |
$2,624
41,824
kWh
|
$1,113
-
kW-mo/yr
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,337 | $80 |
$2,036
32,452
kWh
|
$1,301
-
kW-mo/yr
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,960 | $7,502 |
$1,659
24,579
kWh
|
$1,301
-
kW-mo/yr
|
|
09 | 2.7135: Install occupancy sensors | $2,930 | $896 |
$1,590
25,326
kWh
|
$1,340
-
kW-mo/yr
|
|
10 | 2.7111: Reduce illumination to minimum necessary levels | $1,980 | $440 |
$1,072
17,082
kWh
|
$908
-
kW-mo/yr
|
|
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,631 | $3,190 |
$1,092
17,400
kWh
|
$539
-
kW-mo/yr
|
|
12 | 2.6218: Turn off equipment when not in use | $1,214 | $1,694 |
$657
10,474
kWh
|
$557
-
kW-mo/yr
|
|
13 | 2.4239: Eliminate or reduce compressed air usage | $684 | $2,000 |
$396
6,318
kWh
|
$288
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $126,490 | $34,709 |
$79,274
1,245,528
kWh
|
$47,216
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $93,920 | $30,966 |
$61,151
956,718
kWh
|
$32,769
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs