Assessment Year | 2013 |
---|---|
Principal Product | Surgical appliances and supplies |
NAICS | 339113: Surgical Appliance and Supplies Manufacturing |
SIC | 3842: Orthopedic, Prosthetic, and Surgical Appliances and Supplies |
Sales Range | $100 M to 500M |
# of Employees | 320 |
Plant Area |
67,000
ft2
|
Annual Production | 45
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $84,555 | 1,533,650 |
kWh
|
$0.055 |
Electricity Demand | $47,086 | 4,702 |
kW-mo/yr
|
$10.01 |
Electricity Fees | $32,831 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $59,009 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $55,394 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $16,509 | $3,900 |
$13,204
240,068
kWh
|
$3,305
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $11,217 | $6,000 |
$5,449
99,856
kWh
|
$5,768
-
kW-mo/yr
|
|
03 | 2.7221: Lower temperature during the winter season and vice-versa | $9,040 | $80 |
$5,845
106,271
kWh
|
$3,195
-
kW-mo/yr
|
|
04 | 2.7425: Clean or color roof to reduce solar load | $7,960 | $540 |
$6,368
115,789
kWh
|
$1,592
-
kW-mo/yr
|
|
05 | 2.4323: Use optimum size and capacity equipment | $3,883 | $4,691 |
$2,798
50,874
kWh
|
$1,085
-
kW-mo/yr
|
|
06 | 2.4323: Use optimum size and capacity equipment | $2,564 | $440 |
$570
10,356
kWh
|
$1,994
-
kW-mo/yr
|
|
07 | 2.4323: Use optimum size and capacity equipment | $2,118 | $5,397 |
$1,367
24,856
kWh
|
$751
-
kW-mo/yr
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,942 | $2,196 |
$947
17,233
kWh
|
$995
-
kW-mo/yr
|
|
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,593 | $1,660 |
$1,528
27,788
kWh
|
$65
-
kW-mo/yr
|
|
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $955 | $80 |
$694
12,615
kWh
|
$261
-
kW-mo/yr
|
|
11 | 2.2511: Insulate bare equipment | $686 | $1,520 |
$336
6,112
kWh
|
$350
-
kW-mo/yr
|
|
12 | 2.7135: Install occupancy sensors | $542 | $209 |
$262
4,766
kWh
|
$280
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $59,009 | $26,713 |
$39,368
716,584
kWh
|
$19,641
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $55,394 | $21,027 |
$37,045
674,347
kWh
|
$18,349
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs