Assessment Year | 2013 |
---|---|
Principal Product | Photographic and Optical Equipment/supplies Manufacturing |
NAICS | 333314: Optical Instrument and Lens Manufacturing |
SIC | 3827: Optical Instruments and Lenses |
Sales Range | $10 M to 50M |
# of Employees | 85 |
Plant Area |
97,000
ft2
|
Annual Production | 1,000
bushels
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $221,612 | 2,678,500 |
kWh
|
$0.083 |
Electricity Demand | $29,342 | 6,162 |
kW-mo/yr
|
$4.76 |
Electricity Fees | $38,406 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $42,023 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,241 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $22,474 | $10,160 |
$20,241
243,870
kWh
|
$2,233
-
kW-mo/yr
|
|
02 | 2.7221: Lower temperature during the winter season and vice-versa | $6,857 | $80 |
$6,795
81,870
kWh
|
$62
-
kW-mo/yr
|
|
03 | 2.7496: Install partitions to reduce size of conditioned space | $5,143 | $2,188 |
$4,632
55,812
kWh
|
$511
-
kW-mo/yr
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,086 | $80 |
$1,870
22,537
kWh
|
$216
-
kW-mo/yr
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,565 | $1,660 |
$1,470
17,715
kWh
|
$95
-
kW-mo/yr
|
|
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,104 | $2,406 |
$994
11,983
kWh
|
$110
-
kW-mo/yr
|
|
07 | 2.7496: Install partitions to reduce size of conditioned space | $1,045 | $40 |
$940
11,326
kWh
|
$105
-
kW-mo/yr
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $714 | $205 |
$643
7,743
kWh
|
$71
-
kW-mo/yr
|
|
09 | 2.7496: Install partitions to reduce size of conditioned space | $639 | $1,240 |
$577
6,947
kWh
|
$62
-
kW-mo/yr
|
|
10 | 2.7496: Install partitions to reduce size of conditioned space | $396 | $1,880 |
$358
4,315
kWh
|
$38
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $42,023 | $19,939 |
$38,520
464,118
kWh
|
$3,503
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $36,241 | $16,511 |
$33,311
401,359
kWh
|
$2,930
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs