Assessment Year | 2012 |
---|---|
Principal Product | Fruit Juice Concentrates |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
467,000
ft2
|
Annual Production | 4,500,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,209,860 | 18,060,000 |
kWh
|
$0.067 |
Electricity Demand | $215,491 | 33,360 |
kW-mo/yr
|
$6.46 |
Electricity Fees | $88,271 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $226,335 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $176,461 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $114,097 | $23,031 |
$100,751
1,503,744
kWh
|
$13,346
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $29,492 | $29,008 |
$26,256
364,663
kWh
|
$3,236
-
kW-mo/yr
|
- | |
03 | 2.7425: Clean or color roof to reduce solar load | $27,049 | $190,339 |
$13,453
200,791
kWh
|
$13,596
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $19,052 | $1,660 |
$15,880
237,015
kWh
|
$3,172
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $13,619 | $520 |
$12,026
179,504
kWh
|
$1,593
-
kW-mo/yr
|
- | |
06 | 2.3137: Use power during off-peak periods | $11,955 | $800 | - | - | $11,955 | |
07 | 2.2447: Heat water with exhaust heat | $5,925 | $8,000 |
$3,495
52,162
kWh
|
$2,430
-
kW-mo/yr
|
- | |
08 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $2,502 | $2,372 |
$2,211
32,996
kWh
|
$291
-
kW-mo/yr
|
- | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,598 | $80 |
$1,311
19,563
kWh
|
$287
-
kW-mo/yr
|
- | |
10 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,046 | $255 |
$923
13,771
kWh
|
$123
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $226,335 | $256,065 |
$176,306
2,604,209
kWh
|
$38,074
-
kW-mo/yr
|
$11,955 | ||
TOTAL IMPLEMENTED | $176,461 | $215,885 |
$144,344
2,154,388
kWh
|
$32,117
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs