Assessment Year 2011
Principal Product newpapers
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2752: Commercial Printing, Lithographic
Sales Range $50
M
to 100
M
# of Employees 400
Plant Area 150,000
ft2
Annual Production 80,000
ton
Production Hrs. Annual 8,568
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $331,888 5,863,120
kWh
Electricity Demand $125,212 18,844
kW-mo/yr
Electricity Fees $71,562 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $45,641 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $18,717

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7425: Clean or color roof to reduce solar load $18,841 $46,645 $16,196
284,135
kWh
$2,645
-
kW-mo/yr
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $8,475 $1,320 $8,040
141,047
kWh
$435
-
kW-mo/yr
03 2.7221: Lower temperature during the winter season and vice-versa $8,367 $2,550 $7,191
126,156
kWh
$1,176
-
kW-mo/yr
04 2.7447: Install vinyl strip / high speed / air curtain doors $2,856 $9,183 $2,457
43,112
kWh
$399
-
kW-mo/yr
05 2.7142: Utilize higher efficiency lamps and/or ballasts $2,117 $9,600 $1,519
26,646
kWh
$598
-
kW-mo/yr
06 2.4231: Reduce the pressure of compressed air to the minimum required $1,875 $50 $1,344
23,576
kWh
$531
-
kW-mo/yr
07 2.4322: Use or replace with energy efficient substitutes $1,858 $3,943 $1,597
28,013
kWh
$261
-
kW-mo/yr
08 2.4323: Use optimum size and capacity equipment $1,252 $4,571 $1,028
18,032
kWh
$224
-
kW-mo/yr
TOTAL RECOMMENDED $45,641 $77,862 $39,372
690,717
kWh
$6,269
-
kW-mo/yr
TOTAL IMPLEMENTED $18,717 $3,920 $16,575
290,779
kWh
$2,142
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs