| Assessment Year | 2011 |
|---|---|
| Principal Product | Advertising Novelties |
| NAICS | 339950: Sign Manufacturing |
| SIC | 3993: Signs and Advertising Specialties |
| Sales Range | $50 M to 100M |
| # of Employees | 400 |
| Plant Area |
210,000
ft2
|
| Annual Production | 127,750,000
pieces
|
| Production Hrs. Annual | 4,080
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $243,658 | 4,131,720 |
kWh
|
$0.059 |
| Electricity Demand | $107,736 | 11,354 |
kW-mo/yr
|
$9.49 |
| Electricity Fees | $50,193 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $121,192 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $56,558 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7425: Clean or color roof to reduce solar load | $36,428 | $124,975 |
$28,286
291,605
kWh
|
$8,142
-
kW-mo/yr
|
|
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $27,894 | $2,000 |
$21,659
223,286
kWh
|
$6,235
-
kW-mo/yr
|
|
| 03 | 2.6218: Turn off equipment when not in use | $18,870 | $7,920 |
$14,654
151,073
kWh
|
$4,216
-
kW-mo/yr
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,184 | $41,193 |
$12,568
129,565
kWh
|
$3,616
-
kW-mo/yr
|
|
| 05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $6,322 | $1,275 |
$4,908
50,603
kWh
|
$1,414
-
kW-mo/yr
|
|
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,700 | $1,210 |
$3,905
40,259
kWh
|
$1,795
-
kW-mo/yr
|
|
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,900 | $40 |
$3,495
36,029
kWh
|
$1,405
-
kW-mo/yr
|
|
| 08 | 2.4239: Eliminate or reduce compressed air usage | $4,894 | $2,200 |
$3,803
39,211
kWh
|
$1,091
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $121,192 | $180,813 |
$93,278
961,631
kWh
|
$27,914
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $56,558 | $12,160 |
$43,611
449,599
kWh
|
$12,947
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs