Assessment Year | 2010 |
---|---|
Principal Product | Newspapers |
NAICS | 511110: Newspaper Publishers |
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
126,000
ft2
|
Annual Production | 35,000
ton
|
Production Hrs. Annual | 7,140
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $564,160 | 7,881,343 |
kWh
|
$0.072 |
Electricity Demand | $173,970 | 17,397 |
kW-mo/yr
|
$10.00 |
Electricity Fees | $61,660 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $224,558 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $157,386 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $60,080 | $32,395 |
$52,700
526,996
kWh
|
$7,380
-
kW-mo/yr
|
|
02 | 2.7496: Install partitions to reduce size of conditioned space | $39,832 | $41,440 |
$34,102
252,534
kWh
|
$5,730
-
kW-mo/yr
|
|
03 | 2.7221: Lower temperature during the winter season and vice-versa | $37,971 | $1,020 |
$32,511
325,110
kWh
|
$5,460
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $21,844 | $1,210 |
$18,704
187,039
kWh
|
$3,140
-
kW-mo/yr
|
|
05 | 2.2628: Utilize a less expensive cooling method | $19,608 | $35,500 |
$16,788
167,879
kWh
|
$2,820
-
kW-mo/yr
|
|
06 | 2.7221: Lower temperature during the winter season and vice-versa | $17,417 | $1,020 |
$14,907
149,071
kWh
|
$2,510
-
kW-mo/yr
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $9,898 | $40 |
$7,597
75,973
kWh
|
$2,301
-
kW-mo/yr
|
|
08 | 2.4323: Use optimum size and capacity equipment | $7,732 | $4,531 |
$6,424
64,237
kWh
|
$1,308
-
kW-mo/yr
|
|
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $10,176 | $9,650 |
$8,716
87,160
kWh
|
$1,460
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $224,558 | $126,806 |
$192,449
1,835,999
kWh
|
$32,109
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $157,386 | $45,335 |
$135,135
1,351,349
kWh
|
$22,251
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs