Assessment Year 2010
Principal Product Gears
NAICS 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing
SIC 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified
Sales Range $5
M
to 10
M
# of Employees 84
Plant Area 19,200
ft2
Annual Production 125,000
pieces
Production Hrs. Annual 2,295
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $78,828 1,083,731
kWh
Electricity Demand $30,780 4,054
kW-mo/yr
Electricity Fees $19,245 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $43,170 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $23,674

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7447: Install vinyl strip / high speed / air curtain doors $15,179 $5,366 $10,534
117,041
kWh
$4,645
-
kW-mo/yr
02 2.7221: Lower temperature during the winter season and vice-versa $13,451 $2,000 $9,335
103,729
kWh
$4,116
-
kW-mo/yr
03 2.4322: Use or replace with energy efficient substitutes $5,033 $10,500 $3,443
38,250
kWh
$1,590
-
kW-mo/yr
04 2.7145: Install skylights $4,317 $2,400 $2,996
33,293
kWh
$1,321
-
kW-mo/yr
05 2.7142: Utilize higher efficiency lamps and/or ballasts $3,161 $7,164 $2,194
24,372
kWh
$967
-
kW-mo/yr
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,029 $1,210 $1,407
15,631
kWh
$622
-
kW-mo/yr
TOTAL RECOMMENDED $43,170 $28,640 $29,909
332,316
kWh
$13,261
-
kW-mo/yr
TOTAL IMPLEMENTED $23,674 $20,874 $16,379
181,982
kWh
$7,295
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs