Assessment Year | 2008 |
---|---|
Principal Product | Circuit Boards |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
170,000
ft2
|
Annual Production | 39,500
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $924,085 | 12,164,480 |
kWh
|
$0.076 |
Electricity Demand | $82,204 | 25,584 |
kW-mo/yr
|
$3.21 |
Electricity Fees | $148,104 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $428,536 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $169,953 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $256,906 | $645,000 |
$243,633
2,784,219
kWh
|
$13,273
-
kW-mo/yr
|
|
02 | 2.7221: Lower temperature during the winter season and vice-versa | $60,893 | $2,040 |
$54,667
821,322
kWh
|
$6,226
-
kW-mo/yr
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $32,290 | $43,681 |
$29,715
339,595
kWh
|
$2,575
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $19,060 | $1,210 |
$18,727
214,025
kWh
|
$333
-
kW-mo/yr
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,713 | $40 |
$1,568
17,971
kWh
|
$145
-
kW-mo/yr
|
|
06 | 2.4323: Use optimum size and capacity equipment | $1,677 | $3,475 |
$1,537
17,571
kWh
|
$140
-
kW-mo/yr
|
|
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $33,795 | $22,516 |
$32,049
366,274
kWh
|
$1,746
-
kW-mo/yr
|
|
08 | 2.6218: Turn off equipment when not in use | $22,202 | $3,320 |
$21,008
240,092
kWh
|
$1,194
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $428,536 | $721,282 |
$402,904
4,801,069
kWh
|
$25,632
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $169,953 | $72,807 |
$157,734
1,999,279
kWh
|
$12,219
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs